ECON-4 1.4.0 Global Guide
55
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
-
Default value
-
Force value
NO
Step
-
Comm object
12091
Related applications
ALL
Setpoint visibility
WinScope only
Description
In case the actual RPM differs from Requested RPM for more than RPM window [RPM], the Speed PID
constants fluently change from Speed int to Speed int w and from Speed der to Speed der w. The aim of the
RPM window is to change the speed of regulation (reaction) in case the actual RPM differs significantly from
Requested RPM.
RPM Window
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0-100 %
Default value
10%
Force value
NO
Step
1 %
Comm object
12092
Related applications
ALL
Setpoint visibility
WinScope only
Description
Integration part of the PID regulation loop in case the actual RPM differs from Requested RPM for more than
RPM window.
Speed int w
Setpoint group
Main PID
Related FW
1.4.0
configured ECON-4 extension
module
Range [units]
0,0-100,0 %
Default value
0%
Force value
NO
Step
0.1 %
Comm object
12176
Related applications
ALL
Setpoint visibility
WinScope only
Description
Derivative part of the PID regulation loop in case the actual RPM differs from Requested RPM for more than
RPM window..
Speed der w