6700C Series

Sensor Operated Mixing Faucet

Control Module Settings

IMPORTANT: Always push the Reset Button after any adjustments

1

2

3

4

5

6

7

8

Factory Preset

= Switch Position

Shut Off Time Delay (After hands are removed)

Sw1

Sw2

Sw3

Delay

On

On

On

1 Sec

On

On 

Off

2 Sec

On

Off

On

3 Sec

On

Off

Off

4 Sec

Off

On

On

5 Sec

Off

On

Off

6 Sec

Off

Off

On

7 Sec

Off

Off

Off

8 Sec

Automatic Time Off (maximum run time after activation)

Sw4

Sw5

Time Off

On

On

OFF

On

Off

15 Sec

Off

On

30 Sec

Off

Off

60 Sec

Sensor Distance

Sw6

Mode

Distance

On

Std

4” - 12”

Off

Enhanced

10” - 12”

To increase distance, turn adjuster CLOCKWISE

To decrease distance, turn adjuster COUNTER-CLOCKWISE

Faucet Switch - DO NOT TOUCH

Sw7

Sw8

Mode

On

Off

Auto Faucet

6700C Series

Sensor Operated Mixing Faucet

Control Module Settings

IMPORTANT: Always push the Reset Button after any adjustments

1

2

3

4

5

6

7

8

Factory Preset

= Switch Position

Shut Off Time Delay (After hands are removed)

Sw1

Sw2

Sw3

Delay

On

On

On

1 Sec

On

On 

Off

2 Sec

On

Off

On

3 Sec

On

Off

Off

4 Sec

Off

On

On

5 Sec

Off

On

Off

6 Sec

Off

Off

On

7 Sec

Off

Off

Off

8 Sec

Automatic Time Off (maximum run time after activation)

Sw4

Sw5

Time Off

On

On

OFF

On

Off

15 Sec

Off

On

30 Sec

Off

Off

60 Sec

Sensor Distance

Sw6

Mode

Distance

On

Std

4” - 12”

Off

Enhanced

10” - 12”

To increase distance, turn adjuster CLOCKWISE

To decrease distance, turn adjuster COUNTER-CLOCKWISE

Faucet Switch - DO NOT TOUCH

Sw7

Sw8

Mode

On

Off

Auto Faucet

6700C Series

Sensor Operated Mixing Faucet

Control Module Settings

Settings Control Dipswitches

Reset Button

Sensor Length Adjuster

Summary of Contents for SANI-LAV 512FAL

Page 1: ...ds Free Floor Mount Stainless Steel Wash Station AC Models 512FAL and 512FAL 0 5 Battery Models 512FBL and 512FBL 0 5 of Domestic and Foreign Parts Columbia does not recommend use with harsh chemicals...

Page 2: ...ontrol boxes at desired location on wall 4 Connect power line from sensor to control box 5 Attach supply tube from faucet to control box 6 Connect hot and cold water from the source to mixing check va...

Page 3: ...mm 18 457mm 18 457mm 22 559mm 22 559mm 7 5 191mm 45 120 3048mm 20 508mm 20 508mm 40 1016mm 40 1016mm 117 2972mm 20 508mm 16 5 407mm 5 R 12 7mm 1 5 38mm 2 51mm 1 5 38mm Top 6 152 4mm 875 22mm dia holes...

Page 4: ...4 COLUMBIA SPECIFICATIONS AC OR BATTERY POWERED 800 626 2117 columbiasinks com info columbiasinks com 2021 Columbia Products WASH STATION WITH ELECTRONIC SENSOR Leg Assembly x 18...

Page 5: ...stration C Do not leave salt in the sink or near a saltwater environment Use a quality stainless steel cleaner and follow cleaner instructions Wipe along the grain NOT against Illustration D Things to...

Page 6: ...Plug in Input AC 120V 60 Hz or 220V UL CSA Output DC 12V 0 8A Class 2 Power Cable Armored vandal resistant Optional Multi Unit Adapter Serves up to 8 faucets UL CSA Input AC 120V Output DC 12V 3A Batt...

Page 7: ...e sink wall and tighten the faucet onto the sink using the O Ring 8 Washer 9 and Mounting Nut 10 Attach the 90 Degree Elbow 11 to the Supply Rod 7 USE TEFLON TAPE ONLY NO PIPE DOPE 5 Reconnect the Sen...

Page 8: ...d In line filter is clogged Open clean out trap and check filter screen Clean or replace filter screen Solenoid coil is defective Insert new batteries or reattach power adapter Light blinks but no sol...

Page 9: ...ing 6 Piston Piston Spring and check the Piston Sleeve for corrosion 6 Re install all parts in same order as the diagram below 7 Re install solenoid on the control box and re mount box in water line 8...

Page 10: ...H Sw7 Sw8 Mode On Off Auto Faucet 6700C Series Sensor Operated Mixing Faucet Control Module Settings IMPORTANT Always push the Reset Button after any adjustments 1 2 3 4 5 6 7 8 Factory Preset Switch...