11 | Repair
58 / 76
Operating instructions CMVpro 125-400 | Version 1-en
Fault
Possible cause
Fault discovery
Remedy
Type V: visual inspec-
tion.
Clean and replace
condensate drain/
siphon
_
-
Retrofit with conden-
sate drain.
Loose/defective vibra-
tion absorbers or fas-
tening elements.
Visual inspection
Tightly screw/replace
vibration absorbers
_
and following.
Improper mounting.
Installation location re-
quirements
met
_
.
Fortify foundation
(baseplate). Resize
fastening elements
(anchors).
Overheating of
electric motor.
Bearing or winding
damage.
Auditory inspection,
current draw measure-
ment, winding mea-
surement.
Repair or replace elec-
tric motor
_
Impeller stiff or
stopped.
Visual inspection.
Remove deposits or
foreign objects
_
53].
Motor overload due to
improperly positioned
damper valve.
Measure flow rate and
pressure at the operat-
ing point.
Set damper valve to
proper position.
Motor overload due to
system changes.
Fan/electric motor no
longer meeting the op-
erating point.
Consult with point of
contact (see title
page).
Prohibited op-
erating condi-
tions.
Ductwork not leak
tight.
Check for leakage.
Seal up.
Loose hose clamps or
damaged sleeves.
Re-tighten hose
clamps or replace
sleeves
_
35].
FC parameter "max.
frequency" set improp-
erly (speed too high,
overheating of electric
motor).
Check FC parameters
_
43].
Observe different con-
figuration for PM mo-
tors.
Adjust parameters ac-
cording to characteris-
tic map in technical
data sheet.