2. With a 2.5 mm Allen wrench, tighten the screws so that the slide-in is firmly locked.
3. Insert the plug and slide the cable lock up to the reader and twist the cable lock in place.
Use the DM8000-RS232-02 cable (2.5 meters) or the DM8000-RS232-05 cable (5 meters). For power supply, use the
DataMan 8000 Power Supply (DM100-PWR-000).
Note
: Disconnect the DataMan 8050 reader from power before inserting/removing the communication modules.
Observe the following electrical requirements:
1
6VDC power supply (DM100-PWR-000), a 5.5 mm x 2.1 mm DC Power Plug
2
VCC = +4.75V up to +6.0V for 2.5 m cable
VCC = +5.5V up to +6.0V for 5.0 m cable
WARNING
:
For proper RS-232 operation, do not apply any voltage to pin 9.
Note
: Power on the RS-232 cable can be supplied by either the DC Power Plug or Pin 1 of the D-SUB.
DO NOT
use
both in parallel.
18
Connection Options