Installation
8
2.5
Connecting the 1460 I/O Expansion Module
To connect a 1460 I/O Expansion Module to the In-Sight sensor:
1.
Verify that the 24VDC power supply is switched off.
2.
Connect the power and ground wires from remote I/O devices to terminal blocks on the 1460
I/O Expansion Module.
Figure 2-3: Connecting I/O Wires
a.
Use a flat-head screwdriver to loosen the screw terminals.
b.
Insert wire leads from remote I/O devices into the appropriate positions on the terminal
block. Refer to Section 3.5.4 to verify the assigned signal at each position.
c.
Tighten the screw terminals with the screwdriver to secure the wire leads in the terminal
block.
NOTE
The 1460 I/O Expansion Module outputs labeled HSOUT 0 and HSOUT 1 correspond to
the In-Sight 3400 and 5000 series sensor’s built-in outputs. These signals pass through the
micro-controller on the 1460 I/O Expansion Module without processing. In contrast, the
general-purpose outputs labeled OUT 0 through OUT 7 are lower speed because the
micro-controller processes these signals before they are transmitted to remote devices.