Option 7 of the main menu. From this option it is possible to change the welcome message. The welcome
message is the text that appears on the first line when the control panel is in standby.
This message can have a maximum of 40 characters, which we will enter by means of the control panel
cursors or by using I-Link / Remote software.
3.2.2.11. - General reset/rearm.
Option 8 of the main menu. From this option it is possible to reinitialise the whole system. When
resetting the system all the control panel events are deleted, that is to say, alarms, faults and actuations.
It maintains the state of the out of service elements and/or zones.
3.2.2.12. - Review history
Option 9 of the main menu. In this menu we have 5 submenus: REVIEW COMPLETE HISTORY
,
REVIEW ALARMS
,
REVIEW FAULTS
,
REVIEW DISABLED ITEMS and
REVIEW RELAYS.
By means of the up and down cursors we will move through the various stored events. The events are
stored in chronological order from the most recent to the oldest, storing a maximum of 4095 events.
Once 4095 events are stored, the control panel will automatically delete the oldest in order to store a
new event.
Review complete history:
This enables each of the incidents detected by the control panel to be
reviewed, understanding by incident: disabled alarms, faults, zones and elements and actuations
of relays.
Review alarms:
This submenu is the same as the one to review the complete history except that
is exclusively for alarms.