Microprocessed Voltage Regulator
Three-Phase Perfection Premium Series
User´s Manual
CM COMANDOS LINEARES
- 18/38 -
Functional Check
Once verifying the power outlets, connect any consumer´s equipment, preferably a
personal computer or any piece of equipment with easy visual identification of
operation.
Again, verify the output voltage in the operational condition by feeding the output
charge. The values must be kept in levels within the output precision.
In order to simulate a bypass condition, press one of the arrows on the panel
(above or below) until you reach the
Transfer Bypass? Press Enter
option. Press
the Enter button. A new message
Voltage Regulator Transfer Bypass?
will
be
displayed. Press the Enter button again.
At this point the voltage regulator will switch to bypass, the panel will display the
Bypass Command Activated
message followed by three beeps per second.
To return to the normal condition, select through the arrow the option
Return
Bypass? Press Enter
, press the Enter button and then the
Return Voltage
Regulator Bypass?
message will be displayed. Press the Enter button again. The
voltage regulator will return to the normal operation condition indicating the
Normal
Operation CM
– Comandos Lineares
message on the panel.
Having run these procedures, the voltage regulator is suitable for normal operation
fed by the distribution circuits with stabilized energy.
It is important to verify with the consuming circuits in use, if the consumed values
on the panel, per phase, are within the specified limits in accordance with your
voltage regulator model. These values are indicated on the panel by the power
indications in Watts and VA.
In case of doubt about the total consumption of the critical load, consult
CM
Comandos Lineares´
Applications Engineering Department.
Failure Reset or Alarm, with Connected Load.
In case of failure or alarm indication in the voltage regulator, it is possible to
perform a reset without disconnecting the load already connected. Follow the steps
below:
1. Activate the manual bypass key located in the frontal part of the voltage
regulator to the
on
position.
2. Wait for the
Manual Bypass Activated
indication to appear on the panel.
3. Turn off the manual bypass key. Wait for the display of the message
Press
Enter to Start
.
4. Press the Enter button. The voltage regulator must start. Wait for the
Normal
Operation CM Comandos Lineares
message.
Note.:
If the failure persists, consult
CM Command Lineares
´ Technical
Assistance.
Voltage regulator Operation Recommendation