General technical data - Performance
Size
70.4
75.4
80.4
85.4
90.4
100.4 110.4 120.4 140.4 160.4 180.4 200.4 220.4 240.4
Cooling
Cooling capacity
1
[kW]
218
232
248
269
292
320
351
396
451
504
570
625
676
733
Compressor power input
1
[kW]
45,4
49,0
51,9
56,9
60,5
66,5
73,7
81,4
93,2
105
118
130
142
156
Total power input
2
[kW]
45,5
49,1
52,0
57,0
60,6
66,6
73,8
81,5
93,3
105
119
130
143
156
Partial recovery heating capacity
3
[kW]
42,9
45,8
48,9
53,1
57,5
63,0
69,2
77,8
88,6
99,3
112
123
133
145
EER
1
-
4,80
4,72
4,78
4,73
4,83
4,81
4,76
4,87
4,84
4,81
4,81
4,81
4,75
4,70
Water flow-rate user side / cooling
1
[l/s]
10,4
11,1
11,9
12,8
14,0
15,3
16,8
18,9
21,5
24,1
27,2
29,9
32,3
35,0
Pressure drop user side / cooling
1
[kPa]
28
31
29
34
33
32
34
39
40
43
45
58
56
53
Water flow-rate source side / heating
1
[l/s]
12,6
13,4
14,3
15,6
16,9
18,5
20,3
22,8
26
29,1
32,9
36,1
39,1
42,5
Pressure drop source side / hot
1
[kPa]
22
25
23
27
27
22
22
27
37
37
39
40
38
41
Cooling capacity (EN14511:2013)
4
[kW]
217
231
248
268
292
319
350
395
449
503
568
623
674
731
Total power input (EN14511:2013)
4
[kW]
46,5
50,3
53,2
58,4
61,8
68,1
75,5
83,6
95,7
108
122
133
146
160
EER (EN 14511:2013)
4
-
4,67
4,59
4,65
4,59
4,72
4,68
4,64
4,72
4,69
4,67
4,66
4,67
4,60
4,56
SEER
8
-
6,16
6,24
6,18
6,06
6,01
5,73
5,65
5,91
6,04
5,88
5,88
5,89
5,89
5,89
Cooling capacity (AHRI 550/590)
5
[kW]
218
232
249
270
291
318
350
397
452
506
571
626
677
735
Total power input (AHRI 550/590)
5
[kW]
44,5
48,1
50,9
55,7
59,8
65,8
72,5
79,8
91,4
103
116
127
140
153
COP
R
5
4,90
4,82
4,89
4,85
4,87
4,83
4,83
4,97
4,95
4,91
4,92
4,93
4,84
4,80
IPLV
5
6,75
6,59
6,70
6,62
6,58
6,40
6,54
6,61
6,81
6,64
6,65
6,64
6,54
6,60
Heating
Heating capacity
6
[kW]
249
265
284
308
332
365
400
451
516
576
653
718
778
845
Compressor power input
6
[kW]
55,2
59,6
62,2
69,1
74,0
80,7
89,4
99,1
113
126
144
157
173
190
Total power input
2
[kW]
55,3
59,7
62,3
69,2
74,1
80,8
89,5
99,2
113
126
144
157
173
190
COP
6
-
4,51
4,45
4,58
4,46
4,49
4,53
4,47
4,56
4,58
4,57
4,53
4,57
4,49
4,44
Water flow-rate user side / hot
6
[l/s]
11,9
12,7
13,6
14,7
15,9
17,4
19,1
21,6
24,6
27,5
31,2
34,3
37,2
40,4
Pressure drop user side / hot
6
[kPa]
20
22
21
24
24
19
20
24
34
34
35
36
34
37
Water flow-rate source side / cold
6
[l/s]
9,2
9,8
10,6
11,4
12,3
13,6
14,8
16,8
19,3
21,5
24,3
26,8
28,9
31,3
Pressure drop source side / cold
6
[kPa]
22
25
24
27
26
26
27
31
33
34
36
48
45
43
Heating capacity (EN14511:2013)
7
[kW]
249
266
285
309
333
366
401
453
517
578
655
720
780
847
Total power input (EN14511:2013)
7
[kW]
56,8
61,5
64,2
71,5
76,3
83,5
92,6
103
117
131
150
163
180
197
COP (EN 14511:2013)
7
-
4,39
4,32
4,44
4,32
4,36
4,38
4,33
4,41
4,42
4,41
4,36
4,41
4,33
4,29
The Product is compliant with the Erp (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 2016/2281, also known as Ecodesign Lot21.
‘Contains fluorinated greenhouse gases’(GWP 2087,5)
1. Data referred to the following conditions: Internal exchanger water temperature = 12/7 °C. External exchanger water temperature = 30/35°C. Evaporator fouling factor = 0.44 x 10^(-4) m² K/W
2. The Total Power Input value does not take into account the part related to the pumps and required to overcome the pressure drops for the circulation of the solution inside the exchangers
3. Option. Recovery exchanger water=40/45°C
4. Data compliant to Standard EN 14511:2013 referred to the following conditions: Internal exchanger water temperature = 12/7°C. External exchanger water temperature = 30/35°C
5. Data compliant to Standard AHRI 550/590 referred to the following conditions: internal exchanger water temperature = 6,7 °C. Water flow-rate 0,043 l/s per kW. Entering external exchanger air temperature 35°C. Evaporator fouling
factor = 0.18 x 10^(-4) m2 K/W
6. Data referred to the following conditions: Internal exchanger water temperature = 40/45 °C. External exchanger water temperature = 10/7°C. Evaporator fouling factor = 0.44 x 10^(-4) m² K/W
7. Data compliant to Standard EN 14511:2013 referred to the following conditions: Internal exchanger water temperature = 40/45 °C. External exchanger water temperature = 10/7°C.
8. Data calculated according to the EN 14825:2016 Regulation