23
We make air handling technology. Better.
Air Handling Unit
Installation, Operation, and Maintenance Manual
April 2021
Table 12-4. Service Conditions
Severity of Service
Hours per
day of
Operation
Ambient
Temperature
Maximum
Atmospheric Contamination
Service
Interval
Multiplier
Standard
8
104°F (40°C)
Clean, little corrosion
1.0
Severe
16+
122°F (50°C)
Moderate dirt, corrosion
0.5
Extreme
16+
122°F (50°C)* or
Class H Insulation
Severe dirt, abrasive dust,
corrosion, heavy shock,
vibration
0.1
Low Temperature
<-20°F (<-29°C)**
1.0
*Special high temperature grease recommended (Dow Corning DC44). Dow Corning DC44 is
NOT COMPATIBLE
with other
grease types. Thoroughly purge and clean bearing and cavity before using.
**Special low temperature grease recommended (Aeroshell 7).
Table 12-5. Bearing Sizes and Types
NEMA Frame Size
Bearing Description
[Large bearings (Shaft End) in each frame size]
Bearing
Weight of Grease
to Add in oz (gm)
Volume of Grease to Add
in
3
Teaspoons
56 to 140
6203
0.08 (2.4)
0.15
0.5
140
6205
0.15 (3.9)
0.20
0.8
180
6206
0.19 (5.0)
0.30
1.0
210
6307
0.30 (8.4)
0.60
2.0
250
6309
0.47 (12.5)
0.70
2.5
280
6311
0.61 (17.0)
1.20
3.9
320
6312
0.76 (20.1)
1.20
4.0
360
6313
0.81 (23.0)
1.50
5.2
400
6316
1.25 (33.0)
2.00
6.6
440
6319
2.12 (60.0)
4.10
13.4
5000 to 5800
6328
4.70 (130)
9.20
30.0
5000 to 5800
NU328
4.70 (130)
9.20
30.0
360 to 449
NU319
2.12 (60.0)
4.10
13.4
NOTE:
Not all bearing sizes are listed. For intermediate bearing sizes, use the grease volume for the next
larger size bearing.
Relubrication Procedure:
1. Verify grease being added is compatible with the grease already in the motor.
2. Remove grease outlet plug.
3. With motor stopped, clean all grease fittings with clean cloth.
4. Add recommended amount of grease (Table 12-5).
5. Operate motor for 15 minutes with grease plug removed. This allows excess grease to purge.
6. Reinstall grease outlet plug.
Over-Lubrication can cause excessive bearing temperatures,
premature lubrication breakdown and bearing failure. Do Not
over-lubricate motor.
⚠
CAUTION