Installation Manual PA Pro III
online
–
2018-03-16 Page 19 of 30
7
Configuration of 1-wire sensors
Each 1-wire sensor has a unique ID to identify it on the 1-wire bus and each sensor needs to be
configured/connected in the PA Pro.
The provided 1-wire sensors are already configured and labelled. To add or replace a non-
configured 1-wire sensor, follow the sections below.
Check section 12.3, for troubleshooting.
7.1
Connecting sensors
The sensors need to be connected and configured
one at a time.
Use the following sequence to
setup and connect the sensors:
-
Press ESC to enter the Main menu
-
Press Down until “Setup” is show
n in the display
-
Press SEL to enter setup menu
-
“
1W Sensor Setup
”
appears in the display
-
Press OK to start setup
If this is the first setup
, “T1 Sensor not conf” appears in the display
. If sensors are already
configured, they will be listed.
-
With the up and down arrows go to the position you want to save a sensor to
-
Press SEL
-
“
TX
NEW=xxxxxx OK” is show
n in the display, where TX is the position and xxxxxx is the ID
number of the sensor
-
Confirm with OK
, “S
-
RID Saved” appears for 2 seconds
-
Temperature reading and ID appears in the displa
y “TX=XX.X
ID=xxxxxx”
-
Press up/down to continue with the next sensor or ESC 4 times to go back to the main menu.
If “No new s
-
r found” appears while setting up a new sensor, the PA Pro cannot find any sensor on
the bus that is not already configured. Check the connection and make sure the sensor has not
been configured already.
7.2
Replace a 1-wire senor
To replace a 1-wire sensor:
-
Disconnect old sensor
-
Press ESC to enter the Main menu
-
Press Down until “Setup” is show
n in the display
-
Press SEL to enter setup menu
-
“
1W Sensor Setup
”
appears in the display
-
Press OK
-
Select the sensor number in the list, i
t will say “Sensor missing”.
-
Connect new sensor and press SEL,
-
“
Tx
NEW=xxxxxx OK” is show
n in the display
-
Confirm with OK,
“S
-
RID Saved” appears for 2
seconds
-
Temperature reading and ID appears in the display “TX=XX.X
ID=xxxxxx”
-
Press ESC 4 times to go back to the main menu.
7.3
Clear all 1-wire sensors
To clear all configured 1-wire sensors:
-
Press ESC to enter the Main menu
-
Press Down until “Setup” is show
n in the display
-
Press SEL to enter setup menu
-
Press down until “Clear 1W Sensors” is shown in the display
-
Press OK