background image

1942032 

V1.1   

3 March 2020 

 

   

 

 

   

 

 

 

Clevertest and Clevertest Plus 

 

The Clevertronics Clever-test  units  (LLIFE-PRO-SPOT-CT)  can be programmed to perform 90  minute 

discharge tests at 6-month intervals. A manual test is initiated by pressing the test switch 3 times within a 

5s period (immediate discharge test). A 24 hour delayed test (to allow batteries to fully charge before a 

test) can be initiated by pressing the test switch and hold  for 10  seconds  (i.e., until LED Test Switch 

indicator flashes rapidly). Refer Clever-test Operation Guide for more information. Once the test has been 

completed, maintenance personnel then view the Status Indicator of each fitting to determine a pass or 

failure: 

 

SOLID GREEN

 (not flashing) 

NORMAL – The luminaire is in a normal state charging and awaiting 

next discharge test. 

SLOW YELLOW FLASH

 

(2s Yellow, 2s Off) 

TESTING – The luminaire is currently performing a test. 

VERY SLOW YELLOW & GREEN

 

(4s Yellow, 1s Green) 

RECENTLY PASSED – The luminaire has previously tested and 

passed. This indication remains for 5 days after the completion of the 

test and then changes to SOLID GREEN to indicate a normal state. 

FAST YELLOW & GREEN FLASH

 

(0.5s Yellow, 0.5s Green) 

FAILED LAST TEST – The luminaire has previously tested and failed 

to remain illuminated for the required duration. This indication will 

remain until the required maintenance work has been completed and 

the luminaire passes a subsequent discharge test. 

 

Zoneworks and DATA Monitored Options

 

LLIFE  PROs  with part numbers LLIFE-PRO-SPOT-ZW

,  LLIFE-PRO-SPOT-DATA 

are fitted with 

Zoneworks communications modules (nodes).These fittings are monitored using either Powerline Carrier 

Technology that utilises the power cable to provide data communication or a dedicated data cable to/from 

data routers installed on a dedicated data trunk connected to a central Server (can also be connected via 

Ethernet/Internet/Fibre). Zoneworks software on the server is  used to monitor, coordinate testing and 

collate test data from each Lifelight. Zoneworks LLIFEs can be commissioned by a single push of the test 

switch, or scanning of the supplied barcode. The LED  Test Switch indicator provides a multifunction 

indication of the status of the Lifelight during testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress  LED flashes at 3s On (Yellow) & 0.5s Off 

 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).    For further information of installation of 

a Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. 

DATA version)   

 

DALI EM Option

 

LLIFE PROs with part number 

LLIFE-PRO-SPOT-DALI 

are fitted with DALI modules (nodes) that facilitate 

connection and integration to 3

rd

  Party Lighting  Control Systems.  Before installing the 

LLIFE-PRO-SPOT-DALI, please confirm that the Lighting Control System has the capability to monitor 

DALI Emergency Luminaires.  The LLIFE-PRO-SPOT-DALI will be addressed and configured into the 

control system by the Lighting Control System Commissioning Technicians and not Clevertronics.     

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.    DALI connections 

are marked as Da Da.   

 

 

 

L10

TM

 LIFELIGHT PRO 

Surface Mount Spotlight Emergency 

 

Installation & Maintenance Instruction Leaflet

 

Models:   

LLIFE-PRO-SPOT, LLIFE-PRO-SPOT-DATA, LLIFE-PRO-SPOT-DALI, LLIFE-PRO-SPOT-ZW, 
LLIFE-PRO-SPOT-CT (Note: also applies to the four hour, -4HR, variants) 
240V, 50Hz

 

 

Spare Parts:   

1530230   

Battery, 3.3 Volt 5000mAh Li-ion (Note: 2 battery packs used on the -4HR versions) 

1100869   

Lifelight Pro Head Assembly, Ld:280mm,Rnd,LT,Gen 2 

LLIFE-PRO-CKIT  Lifelight Pro, Control Only, L10 Lithium 
 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before 
installation, ensure that the electricity supply has been switched off and isolated. Installation must be 
carried out in accordance with the relevant Australian and International Standards. 
 
 

Designed in Australia to comply with the 

requirements of AS2293.3: 2005 and AS/NZS 

CISPR15: 2017 

NOTE: Standard product codes with this symbol             

are enabled with Clevertest Plus capability.    Please 

refer to the operation guide supplied with the product for 

details.

 

 

 

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700   

Fax:

 +61 3 9559 2799 

New South Wales

 

Phone:

 +61 2 8805 6400 

Fax:

 +61 2 8805 6444

 

Queensland

   

Phone:

 +61 7 3442 9700 

Fax:

 +61 7 3442 9777 

 

South Australia/Northern Territory

   

Phone:

 +61 8 8301 8800 

Fax:

 +61 8 8351 8286 

 

Western Australia

   

Phone:

 +61 8 9248 3720 

Fax:

 +61 8 9248 3725 

 

New Zealand 

Phone:

 +64 800 548 448

 

 

 

 
 

 

 

 

 

 