Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 

flashing for a period up to 2 minutes. 

 

To access test switch of LLIFE-PRO-RECWP front cover needs to be removed. 

 

Maintained fittings (LLIFE

M

-PRO-xx-yyv-ww) cannot be scanned with a camera using the CleverSparky 

App as the maintained light source interferes with the camera scanning function. To register the fitting 

manually enter the serial number from the QR code and visually read the test result and enter manually 

into CleverSparky. 

 

Zoneworks and DATA Monitored Options

 

LLIFE PROs with part numbers LLIFE-PRO-ZW

,  LLIFE-PRO-DATA 

are fitted with Zoneworks 

communications modules (nodes).These fittings are monitored using either Powerline Carrier Technology 

that utilises the power cable to provide data communication or a dedicated data cable to/from data routers 

installed on a dedicated data trunk connected to a central Server  (can also be connected via 

Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and 

collate test data from each Lifelight. Zoneworks LLIFEs can be commissioned by a single push of the test 

switch  or  scanning of the supplied barcode. The LED  Test Switch indicator provides a multifunction 

indication of the status of the Lifelight during testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress  LED flashes at 3s On (Yellow) & 0.5s Off 

 

In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 

a Zoneworks LW system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. 

DATA version)  

 

DALI EM Option

 

LLIFEs with part numbers 

LLIFE-PRO-DALI 

are fitted with DALI modules (nodes) that facilitate connection 

and integration to 3

rd

  Party Lighting Control Systems.  Before installing the LLIFE-PRO-DALI please 

confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The 

LLIFE-PRO-DALI will be addressed and configured into the control system by the Lighting Control System 

Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned  LED on Solid (Green) 
Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 

A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.  DALI connections 

are marked as Da Da.  

 

 

 

 

 

 

 

 

 

L10™ LIFELIGHT PRO Recessed Emergency

 

Installation & Maintenance Instruction Leaflet

 

 

Designed in Australia to comply with the 

requirements of AS2293.3: 2005 and AS/NZS 

CISPR15: 2011. 

 

NOTE: Standard product codes with this symbol     

are enabled with Clevertest Plus capability.  Please 

refer to the operation guide supplied with the product 

for details.

 

Victoria (Head Office & Manufacturing) 

Website:

 

www.clevertronics.com.au

 

Email:

 

[email protected]

 

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

 

News South Wales

 

Phone: 

+61 2 8805 6400

 

Fax:    

+61 2 8805 6444

 

Queensland

  

Phone:

  +61 7  3442 9700 

Fax:

     +61 7  3442 9777 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

   +61 8 8351 8286 

Western Australia

  

Phone:

 +61 8 9248 3720 

Fax:

   +61 8 9248 3725 

New Zealand 

Phone:

 +64 800 548 448

 

Models:  

 

LLIFEz

-PRO-xx-yyv-ww 

Testing

:

 

 

 

Options

:

 

 

 

 

Manual Test  

xx = Blank 

Maintained 

 z = M 

 

Zoneworks 

xx = ZW 

Non-Maintained 

 z = Blank 

 

Zoneworks DATA    xx = DATA 

Square 

 v=SQ 

 

DALI Compatible      xx = DALI 

Recessed Weatherproof 

 yy=RECWP 

 

Clevertest 

xx = CT 

Reduced Brightness Status LED   yy=RBCIL 

 

 

 

Black (Colour of Head) 

 ww=BLK 

 

(

NOTE: -CT Products supplied with the Clevertest Plus Symbol       are activated with Clevertest PLUS 

capability. Please refer to the operation guide supplied with the product for details). 

Spare Parts:  

1530230 

BATTERY: L10 3.3V 5AH. 200mm lead.Brkt..

 

1100871 

Lifelight Pro Head Assbly,Rnd,Lge+Ring,LT,Blk,Gen2              

1100868 

Lifelight Pro Head Assbly,Rnd,Large+Ring, LT,Gen 2               

LLIFE-PRO-CKIT

 

Lifelight Pro, Control Only, L10

 

LLIFEM-PRO-CKIT 

Lifelight Pro, Maintained, Control Only, L10 

8002917 

PCA: LLPRO RBCIL CT10142-L8 Non-CTP (for use with -RBCIL) 

 

Important:

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 

ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 

accordance with the relevant Australian and International Standards.

 

 

 

 

 

 

 