Cleveland Controls

Division of UniControl Inc

.

Bulletin LTAFS460-10

APPLICATION

The 

Model AFS-460 

is a general purpose 

proving switch with a 

manual reset

 feature 

that requires operator intervention whenever 

it actuates. It can be used to sense positive, 

negative, or differential air pressure in HVAC 

and Energy Management applications that 

require operator interface.

GENERAL DESCRIPTION & 

OPERATION

The plated housing contains a diaphragm, a 

calibration spring and a snap-acting SPST–

NC

 

switch with a manual reset button.

The sample line connections located on 

each side of the diaphragm accept ¼" OD 

rigid or semi-rigid tubing via the integral 

compression ferrule and nut.
An enclosure cover protects the operator 

from accidental contact with the live switch 

terminal screws and the set point adjusting 

screw. The enclosure cover has a 

" opening 

provided to accept a ½" conduit connection.

MOUNTING (SEE FIGURE 1)

Select a mounting location which is free from 

vibration. The 

 AFS-460

 must be mounted 

with the diaphragm in any vertical plane in 

order to obtain the lowest specified operating 

set point. Avoid mounting with the sample 

line connections in the "up" position. Surface 

mount via the two 

3

16

" diameter holes in the 

integral mounting bracket. The mounting 

holes are 3-

" apart. 

(Figure 1)

The sample line connections located on 

each side of the diaphragm accept ¼" OD 

rigid or semi-rigid tubing via the integral 

compression ferrule and nut. However, an 

optional adapter (P/N 18311) is available for 

slipping on ¼" ID flexible tubing For sample 

lines up to 10 feet, ¼" OD tubing is accept-

able. For lines up to 20 feet, use ¼" ID tub-

ing. For lines up to 60 feet, use ½" ID tubing.
Locate the sampling probe a  minimum of 

1-½ duct diameters downstream from the air 

source. Install the sampling probe as close to 

the center of the airstream as possible. Refer 

to 

Figure 2

 to identify the high pressure inlet  

(

H

) and the low pressure inlet (

L

). Select one 

of the following five application options, and 

connect the sample lines as recommended.

POSITIVE PRESSURE ONLY:  

 Connect the 

sample line to inlet 

H

; inlet 

L

 remains open 

to the atmosphere.

NEGATIVE PRESSURE ONLY:

  Connect 

the sample line to inlet 

L

; inlet 

H

 remains 

open to the atmosphere.

TWO NEGATIVE SAMPLES:

  Connect the 

higher negative sample to inlet 

L

. Connect 

the lower negative sample to inlet 

H

.

TWO POSITIVE SAMPLES:

  Connect the 

higher positive sample to inlet 

H

. Connect 

the lower positive sample to inlet 

L

.

ONE POSITIVE AND ONE NEGATIVE 

SAMPLE: 

 Connect the positive sample 

to inlet H. Connect the negative sample to 

inlet L.

Model

AFS–460 

ADJUSTABLE SET POINT AIR PRESSURE SENSING SWITCH WITH MANUAL RESET

AIR SAMPLING  CONNECTION 

(SEE FIGURE 2)