
Section 5 — Commissioning
Hawk 1000
5-16
Part No. 750-366
5.9 Drive Data
If a VFD is present, <Drive Data> will display a read-only screen showing drive output and feedback, Low/
High/Lightoff settings, and current running frequency.
5.10 Ethernet Configuration
Multiple boilers on the same Ethernet network require unique IP addresses. To change a boiler’s configuration,
press the desired field in the “Set New Ethernet Configuration” area. If user is logged in at the proper level, a
numeric keypad will appear. Enter the new data and press the enter key (or use the PV+ keypad). When
finished, go to <Set Enet Config> and when prompted with “Set PLC Ethernet Port Configuration?” press
<Yes>.
Figure 5-28.
After setting a new Ethernet configuration, communication between the HMI and PLC will be lost and must
be reestablished from the HMI. For more information, see “Procedure to Load and Setup a PV+” (available
on the CB portal).
Summary of Contents for Hawk 1000
Page 1: ...750 366 07 2013 Hawk 1000 Boiler Control Operation Manual...
Page 4: ......
Page 6: ......
Page 30: ...Section 3 Hardware Checkout Hawk 1000 3 12 Part No 750 366...
Page 54: ...Section 4 System Configuration Hawk 1000 4 24 Part No 750 366...
Page 78: ...Section 6 Diagnostics and Troubleshooting Hawk 1000 6 6 Part No 750 366...
Page 82: ...Section 7 Parts Hawk 1000 7 4 Part No 750 366...