Vitec Group Communications
Eclipse Median Instruction Manual
2 - 1 2
Figure 2-4: Power supply module’s front door
CONDITIONS THAT CAUSE AN ALARM
The following conditions trigger an alarm:
• If any of the voltages produced by the first power supply unit fall
below normal levels.
• If any of the voltages produced by the second power supply unit fall
below normal levels.
• If an internal matrix alarm condition activates a matrix relay to turn on
an external alarm.
• If the active CPU card exceeds a temperature threshold.
• If either of the CPU cards is removed from the matrix.
• If either of the matrix’s two cooling fans stop operating.
• If the temperature inside the Eclipse matrix exceeds a set threshold.
Power Supply LIghts
+12 Volt Light
+ 5 Volt Light
+3.3 Volt Light
--12 Volt Light
Alarm Lights
Main Alarm Light
External Alarm (EXT ALARM) Light
Temp Alarm Light
Fan-Fail Alarm Light
PSU1 Fail Light
PSU2 Fail Light
Fan-On Alarm Light
Alarm Reset Button
Euro Cassette
Power Supply 1
Euro Cassette
Power Supply 2
Euro Cassette
Alarm Lights
Summary of Contents for Eclipse Median
Page 8: ...Vitec Group Communications Eclipse Median Instruction Manual vi...
Page 20: ...Vitec Group Communications Eclipse Median Instruction Manual 1 8...
Page 68: ...Vitec Group Communications Eclipse Median Instruction Manual 4 1 4...
Page 108: ...Vitec Group Communications Eclipse Median Instruction Manual 8 4...