ClareOne Rate of Rise Heat Detector  
Installation Sheet

 

Last modified:

 05/28/20 

Model Number:

 CLR-C1-HT 

Description 

The ClareOne Rate-Of-Rise heat detector uses a built-in 
thermistor to sample and report on a specific set temperature 
or a sudden rise in temperature.  

Heat

 

– selectable 135F or 200F 

Rate of Rise

 

– rapid temp rise 12F per minute 

Note:

 The device is powered by a 3V lithium battery providing 

up to 10 years of battery life. 

Installation 

Heat detectors are normally installed in areas that are prone to 
smoke such as kitchens and garages. 

Installation notes: 

 

Avoid areas that may have rapidly increasing 
temperatures such as fireplaces, stoves, heaters, etc. 

 

When mounting the detector should be placed on a ceiling 
at least 4 inches away from any wall. If placed on a wall 
the detector must be within 6 inches of the ceiling. 

 

If using the sensor with the heat setting at 135°F make 
sure the ceiling location does not exceed this temperature. 

Setup: 

The detector can be setup to detect a fixed temperature of 
either 135F or 200F. 

Low

 

– 135F 

High

 

– 200F 

Note:

 if no jumper is installed the detector is set to 200F 

To set detection temperature

: Use the jumper to select Low 

or Hi. 

 

Programming 

To add the sensor to your panel and for detailed programming 
instructions, refer to th

C

lareOne Wireless Security and Smart 

Home Panel User Manual

 (DOC ID 1871)

.  

To add the detector:  

1. 

Put the ClareOne panel in “add mode” and follow the 
displayed instructions for adding the sensor.  

2.  Open the sensor body case and depress the tamper 

switch.  

3. 

Exit “add mode.” 

 