Rate of Rise Heat Detector CLR-C1-HT

 

 

The ClareOne Rate-Of-Rise heat detector uses a built-in 

thermistor to sample and report on a specific set temperature or 

a sudden rise in temperature.  

Heat – selectable 135F or 200F 

Rate of Rise – rapid temp rise 12F per minute 

 

Note: The device is powered by a 3V lithium battery providing 

up to 10 years of battery life. 

 

Installation: 

Heat detectors are normally installed in areas that are prone to 

smoke as kitchens and garages. 

 

Avoid areas that may have rapidly increasing temperatures as, 

fireplaces, stoves, heaters, etc. 

 

When mounting the detector should be placed on a ceiling at 

least 4 inches away from any wall. If placed on a wall the 

detector must be within 6 inches if the ceiling. 

 

If using as a 135F make sure the ceiling location does not 

exceed this temperature. 

 

Setup: 

The detector can be setup to detect a fixed temperature of 

either 135F or 200F. 

 

Use the jumper to select Low or Hi: 

 

 

Fixed Temperature 

Low – 135F 

High – 200F 

 

Note: if no jumper is installed the detector is set to 200F. 

 

Programming: 

 

Enrolling 

The panel must learn (program) the detector ID code in order to 

respond to detector signals. For complete programming 

information, refer to the specific control panel documentation.  

 

 

 

 

 

To add the detector to panel memory: 

 

1.  Place the panel in program mode.  

2.  Proceed to the Learn Sensors menu. When the panel 

prompts you for a sensor group number, select the proper 

fire group. 

3.  Select the desired sensor number. When the panel prompts 

you to trip the detector, remove the battery pull tab. (If pull 

tab is already removed, press and then release the tamper 

switch until the panel beeps, indicating successful 

programming.) 

 

                                  

 

 

4.   Exit program mode. 

 

Mounting the Detector 

 

1.  Locate the base mounting holes and mount the base to the 

wall or ceiling with the appropriate hardware (Figure 3). 

2.  Attach the detector to the mounting base. 

 

                                     

 

 

Replacing the Batteries 

Battery life depends on how often the detector transmits signals, 

but is more dependent on the temperature of the installation 

environment. When the battery voltage gets low, the detector 

transmits a low battery signal to the panel. The panel then 

activates trouble beeps to notify the customer that the detector 

battery must be replaced. Pressing the status button identifies 

the sensor with the low battery. 

 

Replace the battery immediately when this condition occurs, 

using the following battery:  

Panasonic CR123A 3V.

 

 

Tamper Switch 

Mounting 

Holes 