CLA-VAL CRL-60 Installation, Operation & Maintenance Manual Download Page 1

DESCRIPTION

The CRL-60 Pressure Relief Control is a direct acting, spring loaded,
diaphragm type relief valve. It may be used as a self-contained valve or
as a pilot control for a Cla-Val Main valve.  It opens and closes within
very close pressure limits.

INSTALLATION

The CRL-60 Pressure Relief Control may be installed in any position.
The control body (1) has one inlet and one outlet port. Body (1) also has
smaller side ports; one on inlet, one on outlet, each with pipe plugs (23)
installed. These smaller side ports are used for control connections or
gauge applications. The body (1) also has one center side port, used as
the sensing line port.  A flow arrow is marked on the body casting.

OPERATION

The CRL-60 Pressure Relief Control is normally held closed by the force
of the compression spring above the diaphragm; control pressure is
applied under the diaphragm.

When the controlling pressure exceeds the spring setting, the disc is lifted
off its seat, permitting flow through the control.

When controlling pressure drops below spring setting, the spring returns
the control to its normally closed position.

ADJUSTMENT PROCEDURE

The CRL-60 Pressure Relief Control can be adjusted to provide a relief
setting at any point within the range found on the nameplate.

Pressure adjustment is made by turning the adjustment screw (11) to
vary the spring pressure on the diaphragm. Turning the adjustment screw
clockwise increases the pressure required to open the valve.
Counterclockwise decreases the pressure required to open the valve.

When pressure adjustments are complete the jam nut (10) should be
tightened and the protective cap (12) replaced.  If there is a problem of
tampering, lock wire holes have been provided in cap and cover.  Wire
the cap to cover and secure with lead seal.

DISASSEMBLY

The CRL-60 Pressure Relief Control does not need to be removed from
the line for disassembly.  Make sure that pressure shut down is accompa-
nied prior to disassembly.  If the CRL-60 is removed from the line for dis-
assembly be sure to use a soft jawed vise to hold body during work.

Refer to Parts List Drawing for Item Numbers.
1.

Remove cap (12), loosen jam nut (10) and turn adjusting 
screw counterclockwise until spring tension is relieved.

2.

Remove the eight screws (15) holding the cover (9). Keep the cover 
and eight screws together and place on a suitable work surface. 
See NOTE under REASSEMBLY.

3.

Remove the cover (9) from body (1).  The spring (8) and two spring 
guides (7).

4.    Remove plug (22) from body (1). Using screwdriver, hold stem  

assembly (4) to remove nut (13).

5.

Slide off the belleville washer (14), upper diaphragm washer (18),  
diaphragm (17) and lower diaphragm washer (19). 

6.

Remove stem guide (21) from body (1). Remove stem assembly (4).
Inspect, replace stem assembly and/or O-rings (5), (6) and (20) if 
necessary. Use soft jawed pliers or vise to hold stem. The polished 
surface of stem must not be scored or scratched.

7.  The seat (3) need not be removed unless it is damaged. If removal 

is necessary use proper size socket wrench and turn counterclock
wise.

INSPECTION

Inspect all parts for damage, or evidence of cross threading.  Check
diaphragm for tears. Check stem assembly (4) for abrasions or other
damage. Check all metal parts for damage, corrosion or excessive wear.

REPAIR AND REPLACEMENT

Minor nicks and scratches may be polished out using 400 grit wet or dry
sandpaper fine emery or crocus cloth.  Replace all O-rings and any
damaged parts.
When ordering replacement parts, be sure to specify parts list item
number and all nameplate data.

REASSEMBLY

In general, reassembly is the reverse of disassembly.  However, the
following steps should be observed:

1. Lubricate the O-Ring (5) and (6) with a small amount of a good grade 

of waterproof grease, (Dow Corning 44 medium grade or equal).    
Use grease sparingly when installing O-ring (20) into guide stem (21).

2. Install stem assembly (4) into guide stem (21).  Use a rotating motion

with minimum pressure to let stem pass through O-ring. Do Not       
Cut O-Ring.

3. Install O-ring (6) at top of stem assembly (4). Install guide stem (21) 

and stem assembly (4) into body (1). Use socket to tighten securely. 
Place lower diaphragm washer (19) on the stem assembly with the  
serrated side up. Position diaphragm (17), upper diaphragm washer 
(18), with serration down, and belleville washer (14) with concave     
side down.

4. Install nut (13) and tighten securely .
5. Continue reassembly as outlined in disassembly steps 1 through 3.

Pressure Relief Control

CRL-60

SYMPTOM

PROBABLE CAUSE

REMEDY

Fails to open.

Controlling pressure
too low.

Back off adjusting
screw until valve
opens.

Fails to open with
spring compression
removed.

Mechanical obstruc-
tion, corrosion, scale
build-up on stem.

Disassemble,
locate,and remove
obstruction, scale.

Leakage from cover
vent hole when con-
trolling pressure is
applied.

Diaphragm Damage

Disassembly replace
damaged
diaphragm.

Fails to close with
spring compressed.

Mechanical obstruc-
tion.

Disassemble, locate
and remove
obstruction.

Fails to close.

No spring compres-
sion.

Re-set pressure
adjustment.

Loose diaphragm
assembly.

Tighten upper
diaphragm washer.

MODEL