NTP-G7 Install the Power and Ground
This procedure installs power feeds and grounds the ONS 15454.
Purpose
ANSI and ETSI:
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Screws
• Ground cable 13.3-mm² (#6 AWG) stranded
• Listed pressure terminal connectors such as ring and fork types; connectors
must be suitable for #10 AWG copper conductors
• Wire cutters
• Wire strippers
• Crimp tool
• Fuse panel
ANSI only:
• Power cable (from fuse and alarm panel to assembly), #10 AWG, copper
conductors, 194 degrees F [90 degrees C])
• Wire wrapper
ETSI only:
• Power cable (from fuse panel to MIC-A/P and to MIC-C/T/P), shipped with
the ONS 15454 ETSI
• Two-hole grounding lug, shipped with the ONS 15454 ETSI
Tools/Equipment
NTP-G4 Open and Remove the FMEC Cover (ETSI Only), on page 60
NTP-G6 Install the MIC-A/P and MIC-T/C/P FMECs (ETSI Only), on page 66
NTP-G5 Remove the Backplane Covers (ANSI Only), on page 63
Prerequisite Procedures
Required
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
This equipment is intended to be grounded. Ensure that the host is connected to earth ground during
normal use.
Statement 39
Warning
Cisco ONS 15454 Hardware Installation Guide
68
Installing the ONS 15454 M12 (ANSI and ETSI) Shelf
NTP-G7 Install the Power and Ground
Summary of Contents for ONS 15454
Page 2: ... 2019 Cisco Systems Inc All rights reserved ...
Page 16: ...Cisco ONS 15454 Hardware Installation Guide xvi Contents ...
Page 28: ...Cisco ONS 15454 Hardware Installation Guide xxviii Preface Preface ...
Page 36: ...Cisco ONS 15454 Hardware Installation Guide 6 Overview Cisco ONS 15454 M6 Shelf ...
Page 510: ...Cisco ONS 15454 Hardware Installation Guide 480 Hardware Specifications Dimensions ...