Step 5
Return to your originating procedure (NTP).
DLP-G561 Mounting the Bracket with Air Deflectors (Front-to-Back) on the
ONS 15454 M6 Shelf for ANSI Rack Configuration
This task installs the bracket with air deflectors (front-to-back) on the ONS 15454
M6 shelf for ANSI rack configuration.
In an ANSI rack, the air deflectors can be mounted only in the 23-inch
rack configuration and in the front position of the chassis.
Note
Purpose
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
Tools/Equipment
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves
Prerequisite Procedures
As needed
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
Use only the fastening hardware provided with the ONS 15454 M6 to prevent loosening, deterioration, and
electromechanical corrosion of the hardware and joined material.
Caution
Procedure
Step 1
(ANSI only) Place the right front air deflector flush against the right side of the chassis (see Diagram 1 of
Step 2
Align the screw holes on the right front air deflector with the screw holes on the right side of the chassis.
Step 3
Insert the screws and tighten them to a torque value of 11.5 in-lb (1.3 N-m).
Step 4
Place the left back air deflector flush chassis as shown in Diagram 2 of
Figure 31: Mounting the Air Deflectors
(Front-to-Back) on the ONS 15454 M6 Shelf for the ANSI rack Configuration, on page 33
Do not mount the left back deflector (exhaust air deflector), if these cards are to be installed in the ONS 15454
M6 shelf:
• 100G-LC-C, 10x10G-LC, or CFP-LC
• EDRA1-26, EDRA1-35, EDRA2-26, or EDRA2-35
Use the standard brackets directly to mount the ONS 15454 M6 shelf.
Step 5
Align the screw holes on the left back air deflector with the screw holes on the left side of the chassis.
Installing the ONS 15454 M6 Shelf
32
Installing the ONS 15454 M6 Shelf
DLP-G561 Mounting the Bracket with Air Deflectors (Front-to-Back) on the ONS 15454 M6 Shelf for ANSI Rack Configuration