Chapter 1 Install the Shelf and Common Control Cards
NTP- G5 Mount the Shelf Assembly in a Rack (One Person)
shows the rack-mounting position for the ONS 15454 ETSI.
Figure 1-3
Mounting an ONS 15454 ETSI in a Rack
Step 3
Using the hex tool that shipped with the assembly, install the two temporary set screws into the holes
that will not be used to mount the shelf. Let the set screws protrude sufficiently to hold the mounting
brackets.
Step 4
Lift the shelf assembly to the desired position in the rack and set it on the screws.
Step 5
Align the screw holes on the mounting brackets with the mounting holes in the rack.
Step 6
Using the Phillips Dynamometric screwdriver, install one mounting screw in each side of the assembly.
Step 7
When the shelf assembly is secured to the rack, install the remaining mounting screws.
Note
Use at least one set of the horizontal screw slots on the shelf assembly to prevent slippage.
Step 8
Using the hex tool, remove the temporary set screws.
Step 9
Return to your originating procedure (NTP).