Status
Color
LED
All diagnostics pass. The module is operational (normal initialization
sequence).
Green
FABRIC
STATUS
Indicates one of the following:
• The diagnostic test has failed. The module is not operational because
a fault has occurred during the initialization sequence.
• The inlet air temperature of the system has exceeded the safe
operating temperature limits of the card (a major environmental
warning). The card has been shut down to prevent permanent damage.
Red
Indicates one of the following:
• The fabric module has just been inserted and is booting up.
• An overtemperature condition has occurred and the module has
powered down.
• The power was turned off with a CLI command.
• The module is resetting and both ejector levers are out.
Flashing red
Power Supply LEDs
Depending on the power supply (AC, DC and HVAC/HVDC power supplies), there are 1 or 2 input LEDs.
The Output, Fault, and ID LEDs have the same function for the AC, DC and HVAC/HVDC power supply
units.
Status
Color
LED
The AC, HVAC/HVDC, or DC input voltage is within the valid range.
Green
Input 1
The AC, HVAC/HVDC, or DC input voltage is outside the valid range.
Off
The DC input voltage is within the valid range.
Green
Input 2
(available
only on DC
power
supply
units)
The DC input voltage is outside the valid range.
Off
The AC or DC output power is within the valid range.
Green
Output
The AC or DC output power is outside the valid range.
Off
The AC or DC output voltage and power supply unit tests are okay.
Off
Fault
Self-diagnostic tests have failed or another power supply failure has occurred.
Flasing red
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
197
OL-30452-01.
LEDs
Power Supply LEDs