Weights
708 lb (321 kg)
FCC as shipped
925 lb (420 kg)
FCC in shipping crate with pallet
1130 lb (513 kg)
FCC, fully loaded with power enclosure,
cards, and cosmetics
Floor Loading
FCC: 6.9 sq ft (0.64 sq m)
FCC in rack footprint(floor contact area)
164 lb/sq ft
Maximum floor loading
Two fan trays
Fabric Chassis Cooling
Up to 1980 cubic feet (56,6000 liters) per minute
FCC airflow
Up to 120 cubic feet (3400 liters) per minute
DC power system airflow
Up to 88 cubic feet (2500 liters) per minute
AC power system airflow
Power Specifications
Table 14: Cisco NCS 6000 FCC Power Specifications
Power Enclosure Components
Either four AC or four DC power trays. AC and DC power trays cannot be mixed.
Power Trays
The AC power tray has three slots for AC PMs. The DC power tray has four slots for
DC PMs.
Power modules (PMs)
Two PCMs are preinstalled in the power enclosure (one per each set of power trays).
Power control modules (PCMs)
AC: Up to 12 power modules can be installed, and only 6 are needed to be active at
any time. This allows support for 6+6 power redundancy by using two independent AC
power sources (6 feeds each).
DC: Up to16 power modules can be installed, and only 8 are needed to be active at any
time. This allows support for 8+8 power redundancy through
“
A
”
and
“
B
”
battery plant
feeds.
Power Redundancy (N+N)
DC Input
–
48 VDC or
–
60 VDC (tolerance range:
–
40 to
–
72 VDC)
Nominal input voltage
Cisco Network Convergence System 6000 Fabric Card Chassis Hardware Installation Guide
128
System Specifications
Power Specifications