DETAILED STEPS
CHAN
‐
PWR
‐
THRESHOLD
‐
CHECK alarm is cleared in one of the these scenarios:
a) The alarm clears automatically when the periodic check determines that the total channel power does not cross failure
thresholds. This scenario occurs when channels are deleted or restored. This increases the total channel power.
b) The alarm must be cleared manually by changing the failure threshold limits.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
CLDRESTART
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
Logical Object: EQPT
The Cold Restart condition occurs when a card is physically removed and inserted, replaced, or when the
NCS power is initialized.
Clear the CLDRESTART Condition
SUMMARY STEPS
1.
Remove and reinsert (reseat) the standby control card.
2.
If the condition fails to clear after the card reboots, complete the
Remove and Reinsert (Reseat) Any Card
procedure.
3.
If the condition does not clear, complete the
Physically Replace a Card, on page 453
procedure for the
card.
DETAILED STEPS
Step 1
Remove and reinsert (reseat) the standby control card.
Step 2
If the condition fails to clear after the card reboots, complete the
Remove and Reinsert (Reseat) Any Card , on page 452
procedure.
Step 3
If the condition does not clear, complete the
Physically Replace a Card, on page 453
procedure for the card.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
COMP-CARD-MISSING
Default Severity: Minor (MN), Non-Service-Affecting (NSA)
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
159
Alarm Troubleshooting
CLDRESTART