Table 48: ASR 5000 PFU Wiring Diagram Descriptions
Description
Item
Two 2-hole lugs are required: one for return (RTN) and one for power (-VDC). The PFU 0.3125-inch
posts spaced 0.88-inch on center.
Method of connection: PFU - Flat Washer - Lug - Lock-Washer - Nut (9/16-inch). The nut(s) must
be torqued to 50 in-lb. (5.65 N-m).
The lug must be covered with heat shrink tubing. The heat shrink tubing should begin approximately
1 inch (25.4 mm) before the lug and extend to within 0.5 inch (12.7 mm) of the lugs first hole. Slide
the tubing over the cable end before crimping the lug to the cable. Refer to the following figure.
Use the Panduit
®
lugs supplied with the chassis (LCD1-56C-E). Crimp them to the cable ends with
a Panduit crimp tool part number CT-920 (die color: green P37 (CD-920-1).
The plastic terminal cover
must
be installed over power and return lugs at all times.
Die angeschlossenen Kabelschuhe muessen mit der Plastikabdeckung gesichert sein.
1
Power Cables (PDP-to-Chassis):
Cable length: Not more than 9 feet (2.7 meters) one way
Voltage drop: 0.3v
Cable size: 1 AWG or greater
2
Power Cables (PDF-to-PDP):
Cable length: not more than 40 feet (12.2 meters) one way
Voltage drop: 0.3v
Cable size: 350,000 Circular Mils
3
Figure 50: Power Lug
Connecting the PFU to the Power Source
Follow the instructions in this section to connect the PFU(s) to the power source.
Each of the four power terminals is shipped with nuts and washers. The PFU has one lock-washer and one
flat washer.
ASR 5000 Installation Guide
129
Cabling the Power Filter Units
Connecting the PFU to the Power Source
Summary of Contents for ASR 5000
Page 16: ...ASR 5000 Installation Guide xvi About this Guide Contacting Customer Support ...
Page 64: ...ASR 5000 Installation Guide 48 Installation Procedure Overview Laser Notice ...
Page 100: ...ASR 5000 Installation Guide 84 Line Card Installation Installing the XGLC ...
Page 122: ...ASR 5000 Installation Guide 106 Cabling the Fast Ethernet 10 100 Line Card FLC2 Interfaces ...
Page 206: ...ASR 5000 Installation Guide 190 Removing and Installing SMC PC Cards Removing PC Cards ...
Page 212: ...ASR 5000 Installation Guide 196 Replacing the Chassis Air Filter Installing the Air Filter ...
Page 220: ...ASR 5000 Installation Guide 204 Replacing a Power Filter Unit What to do with the Failed PFU ...
Page 266: ...ASR 5000 Installation Guide 250 Safety Electrical and EMC Certifications Korean EMC ...
Page 270: ...ASR 5000 Installation Guide 254 Environmental Specifications Chassis Air Flow ...