Wiring
Regardless of the electrical characteristics of the power line, be sure to supply to the Charge
Point with the necessary electrical features indicated at the unit characteristics rating plate,
understood as, supply voltage, grid frequency and required apparent power. In the case that
the power line characteristics are different from those required, any adaptation must be
made to meet these requierements.
The Charge Point has internal electrical protections in each socket-outlet for the protection
of the user against an electrical failure, according to the international standard IEC 61851-
1:2017. In order to guarantee the total protection of the users and the installation (power
supply line included) in front of any electrical hazard, it is mandatory to install a main circuit
breaker (MCB) and a residual current device (RCD) upstream of the charger. These electrical
protections and the rest of the installation have to be aligned with the local and national
rules and the selectivity of the protections has to be guaranteed at all times.
The proper earthing system must be
TT or TN-S.
The ground loop impedance measurement
for the entire installation must be less than
80 ohms
.
The earth resistance of the charging
point could be less if required by national regulations. It is recommended to maintain these
conditions over the years, therefore, technically competent personnel will carry out the
verification of the installation of grounding, at least once a year, at the time when the terrain
is drier.
Before starting wiring connection for the Charge Point
,
the following elements have to be
checked:
• After unpacking the Charge Point, ensure that all electrical components are in good
condition.
• It is recommended to strictly follow the current regulations to determine the appropriate
section of the power cables to feed the Charge Point and at any time as a minimum
comply with indicated in the Thecnical Data here below.
• Make sure the switch (MCCB or fuses) from the main electrical panel from the installation
are cutting the electricity supply during Charge Point installation.
• After the installation, you must seal all holes inside the Charge Point to prevent access
of dirt, foreign objects, animals, etc.
30
Raption
Installation Guide
Summary of Contents for Raption 100
Page 1: ...Raption Series INSTALLATION GUIDE M186A01 03 21D...
Page 2: ...2 Raption Installation Guide...
Page 15: ...15 Installation Guide Raption...
Page 16: ...3 A Dimensions Units specified in millimeters 16 Raption Installation Guide...
Page 56: ...56 Raption Installation Guide...
Page 58: ...58 Raption Installation Guide...
Page 59: ...59 Installation Guide Raption...