background image

 

 

 

13 

 

  Be certain all guards and safety apparatus are installed completely prior to start-up. 

 

  Connect all pressure monitoring and temperature monitoring equipment and confirm they are 

functioning correctly.   

 

  Be certain all down-stream valves, etc., are open.   

 

  Start motor at the intended operating speed.  Slowly close the downstream valves to allow for 

gradual pressure rise

.   

 

  If the pump uses Packing seals: 

 

I

 

NOTE

 

 

Slight leakage is necessary to lubricate the packing during operation. 

 

 

WARNING

 

 

If not appropriately collected, packing leakage may make floor slippery and/or expose personnel 
to hazardous fluids.  Collect packing leakage properly and safely. 

 

  Tighten the packing follower screws in a crossing pattern, gradually, until the packing is evenly 

compressed and the leakage diminishes to near zero, then loosen each of the screws, 
gradually, ¼ turn at a time, until slight leakage occurs.  Slight leakage is necessary in order to 
lubricate the packing and the shaft. 

 

  Be certain to adjust the packing follower properly.   

  Do not over-tighten the packing follower. Over-tightening will cause damage to the packing 

and the shaft. 

  Other sealing options are available. 

 

  Re-adjust the packing follower several times through the running-in period, until the seal is 

thoroughly seated and the rate of leakage is stable. 

 

Operation / Shutdown / Restart 

 

F.1  Heating, Cooling During Operation 

 

If the pump is to be operated outside of room temperature (10°C 

 45°C), care must be taken to ensure the 

process temperature is met and maintained prior to and during operation.  Monitor the pump temperature 
and ensure the target temperature has been met and maintained.  Allow ample time for the pump to adjust 
and stabilize.  Ensure any temperature changes occur gently, thoroughly and evenly (including the seal 
arrangement).  
 
Protect the pump from thermal shocks of greater than 28°C (50°F) / sec.  This could occur from liquid 
entering the pump, from rapid changes in the temperature of the environment of from fire.  Rapid 

temperature changes must be avoided.  Preheating is required when a pump’s operating temperature is 

greater than 28°C (50°F) above ambient temperature. 
 

F.2  Shutdown 

 

The pump may need to be purged of the process fluid during shutdown.  Use of a purging liquid (an inert, 
lubricating liquid which is safe to the pump and personnel,) is recommended, rather than simply attempting 
to drain the process fluid from the pump. 
 

  Run the pump slowly during the purging process in order to ensure no damage occurs. 

 

 

Summary of Contents for 2BIC Series

Page 1: ...Safety and Operation WARNING These instructions should be read thoroughly by all personnel involved with pump operation prior to pump installation operation or maintenance Manual No SRM00100 Rev 02 1...

Page 2: ...Transportation of Pumps 10 D 2 Storage Spare Parts 10 E Installation Start up 11 E 1 General 11 E 2 Tools 11 E 3 Installation Preheating Start up 11 E 3 1 Lubrication Preparation 11 E 3 2 Preheating C...

Page 3: ...s Read observe and follow this manual and the other applicable documents especially all safety instructions and warnings A 2 Other Applicable Documents Document Purpose Product Service Manual Detailed...

Page 4: ...ntially Hazardous Situation Minor Bodily Harm Material Damage Symbol Meaning Safety Warning Take note of all information highlighted by a Safety Warning Sign and follow the instructions to avoid damag...

Page 5: ...flow with minimum fluid pulsation and low pump noise Fluid flowing through the pump provides lubrication for moving parts B 1 2 CIG General Description The CIG is a positive displacement internal gea...

Page 6: ...6 B 2 3 CIG Designation B 2 4 2BIC Designation B 3 Labeling B 3 1 CE Nameplate...

Page 7: ...al knowledge to apply generally accepted safety and operational practices which may not be otherwise covered Every effort was made to prepare the text of this manual so that technical information is c...

Page 8: ...ssure monitoring devices and sealing apparatus are installed and operation prior to starting the pump CAUTION Do not operate the pump while the valves in the system are closed o Pumps may not be used...

Page 9: ...valves can be opened or the blockage removed i NOTE Only trained specialized personnel are qualified to perform maintenance which includes but is not limited to o Inspection o Repair o Assembly o Disa...

Page 10: ...on from hot surfaces and hot liquids must be provided by the operator Take care not to drop the pump Pump weights are clearly and durably marked onto the pump surface Read and consider the weight prio...

Page 11: ...p housing WARNING On critical or dangerous equipment provide safety and emergency systems to protect personnel and property from injury due to pump malfunction If pumped liquids are flammable toxic co...

Page 12: ...other cool liquid to the surface If the pump is to be preheated or cooled prior to installation heat or cool the pump to the operating temperature by use of an approved method such as a band heater ba...

Page 13: ...are available Re adjust the packing follower several times through the running in period until the seal is thoroughly seated and the rate of leakage is stable F Operation Shutdown Restart F 1 Heating...

Page 14: ...ing power to driver Shut wire or chain and lock all valves in pump inlet outlet piping If applicable shut off any steam or other fluid supply lines to the pump Visually check equipment frequently for...

Page 15: ...Installation of spare parts should only be performed by trained specialized personnel in conjunction with the appropriate Original Installation Care and Maintenance Instructions H Failure All failures...

Page 16: ...2018 CIRCOR Pumps North America LLC All rights reserved CIRCOR 1710 Airport Road P O Box 5020 Monroe NC USA 28111 5020 Tel 704 289 6511 Website www circorpt com e mail cc circor com...

Reviews: