Wiring and protections
A
A
B
Cable
glands M32
This Charge Point is designed to be permanently connected to an AC supply network.
Use provided cable glands in order to maintain the IP protection
MCB RCD 3
The IEC-61851-1:2017 standard indicates that each
plug shall have protections. In case the Charge
Point has no protections inside, they shall be placed
upstream. These protections shall be as follows:
1.Main circuit electrical protections :
-
MCB
(One per each charging outlet ) overload and
short-circuits protection ,must be curve C with gauge
25% higher than the current setup of the charger
controller. with 2P ( 230 Vac in single phase variant) or
4P ( 400 Vac in three phase variant) according to the
standards: IEC 60898-1, IEC 60947-2 or IEC 61009-1.
For example for 32A setup a 40A MCB will be used)
- RCD
(One per each charging outlet) direct and indirect contacts RCD must be at least Type A and with a
sensitivity of 30 mA or RCD type B with the same rating. The gauge of this electric protections must be
according to the current setup of the charge controller . C fault current shall be measured by a RCD type B or
a appropriate equipment that ensures the disconnection of the supply in case of DC fault current above 6 mA.
( eNext Elite may be equipped with and integrated 6mA. DC leakage detection ) With 2P ( 230 Vac in single
phase variant) or 4P ( 400 Vac in three phase variant) according to the standards: IEC 60898-1, IEC 60947-2
or IEC 61009-1
2. Auxiliar Circuit
(Optional just in case of selecting wiring 2A, view pag 19)
:
-
MCB
overload and short-circuits protection with 2 Poles 6A
In all cases, coordination with the protections installed upstream must be guaranteed.d
NOTE: According to some national regulations RCD Type B or Type A with 6mA DC leakage detection may be mandatory.
SECTION [mm2]
Suggest
Maximum
Observations
Ma
in Circuit (Power supply
)
6 / 10
10
6mm2* only if it includes an auxiliary circuit
Aux. Circuit (Control circui
t)
2,5
4
Trip Coil
2,5
4
Summary of Contents for Wallbox eNext Series
Page 1: ...Installation Manual Wallbox eNext Series ...
Page 2: ...Wallbox eNext Series Installation Manual ...
Page 4: ...Wallbox eNext Series Installation Manual ...
Page 6: ...02 Wallbox eNext Series Installation Manual 1 ...
Page 11: ...07 ...
Page 14: ...10 Wallbox eNext Series Installation Manual 4 Dimensions in mm 39 335 315 200 335 ...
Page 15: ...11 Dimensions 168 52 5 105 230 52 5 62 5 34 34 62 5 39 5 255 20 5 ...
Page 19: ...15 C Positioning Drill the wall Drill bit M 6 8 Dimensions in mm 1100 255 230 115 ...
Page 32: ...28 Wallbox eNext Series Installation Manual 7 ...
Page 34: ...30 Wallbox eNext Series Installation Manual 8 ...
Page 35: ...31 Notes ...