 Cimetrics BACnet/IP to Utility Meters User Manual    Cimetrics Inc. 

 

 

 

  

 
Cimetrics Inc. 

  

B6070  
BACnet/IP to Utility Meters 
 
 

  

 

 
 
 

User Manual 

 

Revised September 2018 

 

 
 

Summary of Contents for B6070

Page 1: ...B6070 Cimetrics BACnet IP to Utility Meters User Manual Cimetrics Inc 1 Cimetrics Inc B6070 BACnet IP to Utility Meters User Manual Revised September 2018...

Page 2: ...troduction 2 Wiring Instructions 4 Logging to B6070 5 Router Configuration 6 1 B3060 web interface overview 6 2 BACnet Device Settings 7 3 BACnet Network Settings 8 4 BBMD Setting of the BACnet networ...

Page 3: ...urther rate limited by count software logic which will only accept rates below 60 pulses per second The above being said about the inputs they are perfectly suited to interface to dry contact form C r...

Page 4: ...t Demand calculation is present Then we have three other derived measures for each channel which are effectively controlled by resets Resets are initiated by the Reset command One derived measure is a...

Page 5: ...ecially modified version with the excitation sources removed or disabled Hook the ChX to high or side of the solid state output Hook the ChX to low or side of the solid state output Reverse if current...

Page 6: ...s to 192 168 88 90 with a subnet mask of 255 255 255 252 Open your browser and enter the following URL http 192 168 88 89 admin You will be prompted to login User admin password admin For improved acc...

Page 7: ...hanged Once you have successfully logged in you will see the home page which shows some basic information about the B3060 To select a page you should click on the menu item on the left side of B3060 s...

Page 8: ...vice Settings This page allows you to view modify BACnet Device settings of the BBMD Make sure that the Device Instance Number and Device Name are unique across the whole BACnet internetwork Keep in m...

Page 9: ...B6070 Cimetrics BACnet IP to Utility Meters User Manual Cimetrics Inc 8 3 BACnet Network Settings Here you specify or modify BACnet network settings or restore them to the factory default settings...

Page 10: ...Setting of the BACnet network This page allows to view or modify BBMD settings attached to the BACnet network To modify Advanced BBMD settings click on Advanced button it will open up advanced BBMD p...

Page 11: ...B6070 Cimetrics BACnet IP to Utility Meters User Manual Cimetrics Inc 10...

Page 12: ...ount Settings Here you can change login information Keep in mind that you can never change your assigned admin password which is printed on a label on the bottom of the B3060 You can however create on...

Page 13: ...shows statistics for the routing table in B3060 Foreign Devices subscribed to B3060 BBMD and information about B3060 interfaces Looking at this page you can quickly find out what is happening on your...

Page 14: ...d the configuration for archive purposes Note that passwords are not contained in the configuration file All configuration editing should be done via the B3060 s web interface not in downloaded files...

Page 15: ...tivate Configuration Once changes are made to any configuration on the B3060 the changes get saved only after clicking on the Confirm button in the Activate Configuration screen Clicking on this will...