18 - SERVICING AND MAINTENANCE

Before working on the unit, disconnect it from its electrical power source. For units equipped with orange terminals, raise all the orange 

breaking devices and cut the 2 circuit breakers.

Working on the compressor:

 

-

The compressor is fastened to the platform by four dia. 8 mm screws.

Warning: Do not tighten these screws to a torque of more than 13 Nm.
If you do not have a torque wrench, tighten them until they are snug then tighten a further ¾ turn.

Recommendations:

Take the operating readings and perform the checks listed in the table on the previous page at least once a year.

To ensure your unit runs smoothly and to obtain service under the warranty, take out a maintenance contract with your installer or an 

approved maintenance company.

With the unit running, check it thoroughly for any abnormal visual signs or noises.

Make sure there are no traces of oil around the unit.

Specific details and mandatory checks relating to the use of refrigerant fluid

In accordance with Regulation (EC) No. 842/2006 on certain greenhouse gases.

R410A refrigerant fluid is a gas which has the following impact on the environment:

1.  No impact on the OZONE layer: ODP

 (Ozone Depletion Potential) rating = 0.

2. 

Impact on the greenhouse effect: GWP

 (Global Warming Potential) = 2088.

 

-

Users must have units containing over 3 kg of refrigerant periodically checked for leaks by qualified personnel (2 kg in France, 

decree and order of 7 May 2007). Regardless of the refrigerant charge in your system, CIAT requires that this check be carried out 

in order to keep your system in good working order.

 

-

Users of any system containing over 3 kg of refrigerant (2 kg in France) are required to keep a log of the quantities and types of 

refrigerants used, added or recovered, and to include the dates and results of leak checks. The name of the technician and his 

company must also be recorded. CIAT strongly recommends keeping such a log even if the refrigerant load of your system does 

not require one.

 

-

A leak check must be carried out one month after any leak repairs.

 

-

System users are responsible for collecting used refrigerant and having it recycled, regenerated or destroyed. 

Mandatory check each year
Detection of leaks on the refrigerating circuit.
Clean the coil:

 

-

Remove the unit's cover (see procedure in electrical connection section)

 

-

Using a vacuum cleaner, carefully clean the coil and the entire blower compartment.

 

-

Put the cover back in place.

Clean the unit's pan.

 

 EN-13 

 CONDENCIAT

®

 CL2

Summary of Contents for CONDENCIAT CL2

Page 1: ...Instruction manual 11 2021 EN7579254 01 CONDENCIAT CL2 11 2021 EN7579254 01 ...

Page 2: ......

Page 3: ...HANDLING 5 8 OPERATING LIMITS 5 9 TECHNICAL SPECIFICATIONS 5 10 ELECTRICAL SPECIFICATIONS 5 11 DIMENSIONS 6 12 INSTALLATION 8 13 ELECTRICAL CONNECTIONS 9 14 SETTING THE CONTROL AND SAFETY DEVICES 9 15 REFRIGERANT CONNECTIONS 10 16 PRESSURE AND CHARGE TEST 11 17 COMMISSIONING 12 18 SERVICING AND MAINTENANCE 13 19 TROUBLESHOOTING 14 20 DECLARATION OF CONFORMITY 15 21 WARRANTY 15 CONTENTS ...

Page 4: ...rant Presence of voltage Site of installation Temperatures up to 150 C Only experienced and qualified persons may work on this equipment The recommendations and instructions given in the maintenance brochures and the special instructions on the labels must be followed Always comply with applicable standards and regulations IMPORTANT before carrying out any work on the unit make sure it is powered ...

Page 5: ... tubes aluminium fins Fan Type Propeller Quantity 1 2 Nominal flow rate m3 h 2350 2770 4700 5540 5000 Speed RPM 700 904 700 904 Weight kg 69 69 101 112 118 Refrigerant connections Liquid line inch 3 8 1 2 Gas line inch 5 8 3 4 7 8 10 ELECTRICAL SPECIFICATIONS CONDENCIAT CL2 28 35 50 65 75 Compressor Voltage 400 V 3 Ph 50 Hz Maximum current A 6 9 8 0 10 3 15 0 15 0 Fans Maximum current A 0 46 0 97 ...

Page 6: ...ance 350 350 100 100 170 602 1035 263 410 27 705 377 5 45 450 5 B C 2 holes Ø8 2 100 263 602 170 A 20 20 410 for fixing the mounts to the floor Detail A Position of holes for fixing the anti vibration mounts to the floor Four fixing points HM8 x 55 screw 90 B C 137 5 Outdoor air flow direction B LIQUID line C INTAKE GAS line CONDENCIAT CL2 EN 6 ...

Page 7: ...0 5 B C 27 1305 600 377 5 45 2 holes Detail A Position of holes for fixing the anti vibration mounts to the floor 4 fixing points HM8 x 55 screws for fixing the mounts to the floor Ø8 2 100 A 20 20 410 263 602 170 90 B C 137 5 Outdoor air flow direction B LIQUID line C INTAKE GAS line Anti vibration mounts are fitted to the heat pump using 4 x HM8 screws 55 mm in length EN 7 CONDENCIAT CL2 ...

Page 8: ...n Min Min Installation on soft ground 200 mm 200 mm Concrete foundations Installation on concrete ground 200 mm 200 mm Concrete foundation Nothing should obstruct the free flow of air over the air cooled exchanger Adhere to the minimum distances shown above Protect from prevailing winds CONDENCIAT CL2 EN 8 ...

Page 9: ...eristics the distance of the unit from the main supply point the upstream protection and the neutral operating conditions IMPORTANT Connect the unit to earth before making any other electrical connections A main cut off switch must be installed on the unit Cable routing Detail of electrics box supply External control input this potential free dry contact positioned between terminals 1 and 2 is use...

Page 10: ... and deoxidised suitable for an operating pressure of at least 4200 kPa and minimum burst pressure of 20 700 kPa Domestic water type copper pipes must never be used Smooth the ends of the pipes by inclining them downwards Make sure there is no contamination inside the pipes Remove the flare nuts from the unit and place them on the pipe Flare the ends of the pipes Characteristics of a properly flar...

Page 11: ...ressure pressostat Before starting up the compressor check that the operations below have been carried out Electrical connection check that all the connections are correctly tightened and that the voltage is stable and in accordance with the data on the manufacturer s data plate Connecting the refrigeration lines Pressure test Evacuation To charge with R410A fluid if it is not possible to fill the...

Page 12: ...evented Date Time CONDENCIAT CL2 operating readings System start up date Serial No Installer Site of installation Model 28o 35o 50o 65o 75o Compressor Suction pressure bar Intake temperature C Condensation pressure bar Condensing temperature C Air cooled condenser Gas inlet temperature C Liquid outlet temperature C Air inlet temperature C Air outlet temperature C Nominal voltage V Voltage at termi...

Page 13: ...ment 1 No impact on the OZONE layer ODP Ozone Depletion Potential rating 0 2 Impact on the greenhouse effect GWP Global Warming Potential 2088 Users must have units containing over 3 kg of refrigerant periodically checked for leaks by qualified personnel 2 kg in France decree and order of 7 May 2007 Regardless of the refrigerant charge in your system CIAT requires that this check be carried out in...

Page 14: ... very low b Power supply cable disconnected a Check the line voltage and locate the voltage drop b Check the connections The compressor stops and starts repeatedly a External control contact cycling too rapidly a Insufficient gas c Evaporator fouled d The evaporator fan or accelerator pump is not working e Expansion device damaged or blocked by impurities f Dehumidifier filter blocked a Adjust the...

Page 15: ... Conformity This unit complies with the requirements of Electrical Equipement Safety Regulations 2016 Electromagnetic Compatibility Regulations 2016 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2012 UK Importer Toshiba Carrier UK Ltd Porsham Close Roborough Plymouth PL6 7DB 21 WARRANTY See our general terms and conditions of sale EN ...

Page 16: ...Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in the European Union Manufacturer reserves the right to change any product specifications without notice ...

Reviews: