5.2 - Physical data ILD 602R - 2000R
AQUACIAT
POWER™
ILD
0602R
0700R
0800R
0900R
1000R
1150R
Sound levels
Unit + High temperature option/Nominal high performance
Sound power
(1)
dB(A)
90,5
91,0
91,5
92,0
92,0
93,0
Sound pressure at 10 m
(2)
dB(A)
58,5
59,0
59,5
60,0
60,0
61,0
Standard unit
Sound power
(1)
dB(A)
88,0
88,5
89,0
89,5
89,5
90,5
Sound pressure at 10 m
(2)
dB(A)
55,5
56,0
56,5
57,0
57,0
58,0
Unit + Very Low Noise option
Sound power
(1)
dB(A)
85,0
86,0
86,5
87,0
87,0
88,0
Sound pressure at 10 m
(2)
dB(A)
53,0
53,5
54,0
54,5
54,5
55,5
Unit + Ultra Low Noise option
Sound power
(1)
dB(A)
83,0
84,0
84,5
85,0
85,0
86,0
Sound pressure at 10 m
(2)
dB(A)
51,0
52,0
52,5
53,0
53,0
54,0
Dimensions
Standard unit
Length
mm
2410
2410
2410
2410
2410
3604
Width
mm
2253
2253
2253
2253
2253
2253
Height
mm
2324
2324
2324
2324
2324
2324
Unit + water buffer tank module option
Length
mm
3604
3604
3604
3604
3604
4798
Operating weight
(3)
Standard unit
kg
1569
1575
1784
1811
1817
2394
Unit + Ultra Low Noise option
kg
1672
1678
1918
1946
1952
2552
Unit + Ultra Low Noise + HP dual-pump hydraulic module option
kg
1808
1814
2065
2092
2098
2747
Unit + Ultra Low Noise + HP dual-pump hydraulic Water
buffer tank module option
kg
2791
2797
3048
3075
3081
3756
Compressors
Hermetic Scroll 48.3 r/s
Circuit A
1
1
2
2
2
2
Circuit B
2
2
2
2
2
3
Number of power stages
3
3
4
4
4
5
Unit PED category
III
III
III
III
III
III
Refrigerant
(3)
R-32 / A2L/ GWP= 675 in accordance with ARI4
Circuit A
kg
10,50
10,50
16,00
16,00
16,00
16,00
tCO
2
e
7,1
7,1
10,8
10,8
10,8
10,8
Circuit B
kg
16,00
16,00
16,00
16,00
16,00
28,50
tCO
2
e
10,8
10,8
10,8
10,8
10,8
19,2
Oil
Circuit A
l
6,6
6,6
13,2
13,2
13,2
13,2
Circuit B
l
13,2
13,2
13,2
13,2
13,2
22,8
Capacity control
Connect’Touch
Minimum capacity
%
33
33
25
25
25
20
Condenser
Grooved copper tubes and aluminium fins
Fans
Axial with rotating impeller
Standard unit
Quantity
3
3
4
4
4
5
Maximum total air flow (cooling mode)
l/s
11790
11790
15720
15720
15720
19650
Maximum rotation speed (heating mode)
r/s
12
12
12
12
12
12
Maximum total air flow (heating mode)
l/s
14460
14460
19280
19280
19280
24100
Maximum rotation speed (heating mode)
r/s
16
16
16
16
16
16
Evaporator
Dual-circuit plate heat exchanger
Water volume
l
16,2
16,2
16,2
20,7
20,7
38,7
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air vent valve,
pressure sensors
Pump
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure
(as required), single or dual (as required)
Expansion tank volume (Option)
l
50
50
50
50
50
80
Buffer tank volume (optional)
l
550
550
550
550
550
550
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic
®
type
Connections
inches
3
3
3
3
3
4
External diameter
mm
88,5
88,6
88,7
88,8
88,9
114,3
Casing paint colour
Colour code RAL 7035 & 7024
(1) In dB ref=10
-12
W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in accordance
with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information, calculated
from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
5 - PHYSICAL AND ELECTRICAL DATA FOR THE UNITS
EN-11
AQUACIAT
POWER
™ LD/ILD
Summary of Contents for AQUACIAT POWER LD 1100R
Page 1: ...AQUACIAT POWER LD 602R 3500R ILD 602R 2000R 12 2021 10590 Instruction manual...
Page 81: ...EN 81 AQUACIATPOWER LD ILD...
Page 82: ......
Page 83: ......