background image

14 - STANDARD MAINTENANCE

The heat pumps must be maintained by professional technicians, 

whilst routine checks can be carried out locally by specialised 

technicians. See the standard EN 378-4.

All refrigerant charging, removal and draining operations 

must be carried out by a qualified technician and with the 

correct material for the unit. Any inappropriate handling can 

lead to uncontrolled fluid or pressure leaks.

Before doing any work on the machine ensure that 

the power is switched off. If a refrigerant circuit is 

opened, it must be evacuated, recharged and tested 

for leaks. Before any operation on a refrigerant 

circuit, it is necessary to remove the complete 

refrigerant charge from the unit with a refrigerant 

charge recovery group.

Simple preventive maintenance will allow you to get the best 

performance from your heat pump unit:

 

-

improved heating performance

 

-

reduced power consumption

 

-

prevention of accidental component failure

 

-

prevention of major time-consuming and costly interventions

 

-

protection of the environment

There are five maintenance levels for the heat pump units, as 

defined by the AFNOR X60-010 standard.

14.1 - Level 1 maintenance

See note on the next page. Simple procedures, can be carried 

out by the user on a weekly basis:

 

-

Visual inspection for oil traces (sign of a refrigerant leak),

 

-

Air heat exchanger (evaporator) cleaning - see chapter 

‘Evaporator coil - level 1’,

 

-

Check for removed protection devices, and badly closed 

doors/covers,

 

-

Check the unit alarm report when the unit does not work (see 

Aquaciat Caléo™ TD Connect Touch control manual),

 

-

General visual inspection for any signs of deterioration,

 

-

Verify the charge in the sight-glass,

 

-

Check that the temperature difference between the heat 

exchanger inlet and outlet is correct.

14.2 - Level 2 maintenance

This level requires specific know-how in the electrical, hydraulic 

and mechanical fields. It is possible that these skills are available 

locally: existence of a maintenance service, industrial site, 

specialised subcontractor.
The frequency of this maintenance level can be monthly or 

annually depending on the verification type.

In these conditions, the following maintenance operations are 

recommended.
Carry out all level 1 operations, then:Electrical checks

 

-

At least once a year tighten the power circuit electrical screw 

connections (see table with tightening torques).

 

-

Check and retighten all control/command screw connections, 

if required (see table with tightening torques).

 

-

Remove the dust and clean the interior of the control boxes, 

if required.

 

-

Check the status of the contactors and disconnect switches.

 

-

Check the presence and the condition of the electrical 

protection devices.

 

-

Check the correct operation of all heaters.

 

-

Replace the fuses every 3 years or every 15000 hours (age-

hardening).

 

-

Check that no water has penetrated into the control box.

Mechanical checks

 

-

Check the tightening of the fan tower, fan, compressor and 

control box fixing bolts.

Water circuit checks

 

-

Check the water connections.

 

-

Purge  the  water  circuit  (see  chapter  ‘Water  flow  control 

procedure’).

 

-

Clean the water filter (see chapter ‘Water flow control 

procedure’).

 

-

Check the operation of the flow switch.

 

-

Check the status of the thermal piping insulation.

 

-

Check the concentration of the anti-freeze protection solution 

(ethylene glycol or polyethylene glycol).

Refrigerant circuit

 

-

Fully clean the air evaporators with a low-pressure jet and a 

bio-degradable cleaner (counter-current cleaning - see 

chapter ‘Evaporator coil - level 2).

 

-

Check the unit operating parameters and compare them with 

previous values.

 

-

Carry out an oil contamination test. Replace the oil, if 

necessary.

 

-

Check the operation of the high-pressure switches. Replace 

them if there is a fault.

 

-

Check the fouling of the filter drier. Replace it if necessary.

 

-

Keep and maintain a maintenance sheet, attached to the unit.

All these operations require strict observation of adequate 

safety measures: individual protection garments, compliance 

with all industry regulations, compliance with applicable 

local regulations and using common sense.

14.3 - Level 3 (or higher) maintenance

The maintenance at this level requires specific skills/approval/

tools and know-how and only the manufacturer, his representative 

or authorised agent are permitted to carry out these operations. 

These maintenance operations concern for example:

 

-

a major component replacement (compressor, condenser),

 

-

any intervention on the refrigerant circuit (handling refrigerant),

 

-

changing of parameters set at the factory (application change),

 

-

removal or dismantling of the unit,

 

-

any intervention due to a missed established maintenance 

operation,

 

-

any intervention covered by the warranty.

To reduce waste, the refrigerant and the oil must be 

transferred in accordance with applicable regulations, using 

methods that limit refrigerant leaks and pressure drops and 

with materials that are suitable for the products.
Any detected leaks must be repaired immediately.
The compressor oil that is recovered during maintenance 

contains refrigerant and must be treated accordingly.
Refrigerant under pressure must not be purged to the open 

air.
If a refrigerant circuit is opened, plug all openings, if the 

operation takes up to one day, or for longer periods charge 

the circuit with nitrogen.

NOTE:  Any  deviation  or  non-observation  of  these 

maintenance criteria will render the guarantee conditions 

for the unit nul and void, and the manufacturer, CIAT, will 

no longer be held responsible.

 

 EN-35  AQUACIAT

CALÉO™

 TD

Summary of Contents for AQUACIAT CALEO TD 100

Page 1: ...AQUACIAT CAL O High temperature heat pumps 03 2022 10198 Instruction manual...

Page 2: ...6 APPLICATION DATA 19 6 1 Unit operating range 19 6 2 Plate heat exchanger water flow 19 6 3 Minimum water flow rate 19 6 4 Maximum plate heat exchanger water flow rate 19 6 5 Water loop volume 20 6...

Page 3: ...S WITH FANS WITH AVAILABLE PRESSURE FOR INDOOR INSTALLATION XTRAFAN 34 13 1 Fan discharge connection 34 13 2 Applicable rules for units incorporated into an air duct system 34 13 3 Electrical data for...

Page 4: ...uits are intact especially that no components or pipes have shifted or been damaged e g following a shock If in doubt carry out a leak tightness check If damage is detected upon receipt immediately fi...

Page 5: ...he units are intended to be stored and operate in an environment where the ambient temperature must not be less than the lowest allowable temperature indicated on the nameplate Do not introduce signif...

Page 6: ...Protection device checks If no national regulations exist check the protection devices on site in accordance with standard EN378 once a year for the high pressure switches every five years for extern...

Page 7: ...he certified dimensional drawings for the units It is dangerous and illegal to re use disposable non returnable reclaim cylinders or attempt to refill them When reclaim cylinders are empty evacuate th...

Page 8: ...ximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components see dimensional drawings the number of support points is adequate and th...

Page 9: ...2 577 18 TD 120 to 150 X mm Y mm Z mm 841 31 521 7 563 33 TD 200 to 300 Unit with grille protection option X mm Y mm Z mm 798 25 568 22 577 18 NOTES 1 Material self adhesive vinyl 9800 2 The symbols m...

Page 10: ...an installation For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four...

Page 11: ...e location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side cleara...

Page 12: ...st when designing an installation For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installa...

Page 13: ...r the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side cl...

Page 14: ...For the location of fixing points weight distribution and coordinates of the centre of gravity refer to the certified dimensional drawings B In multiple unit installations maximum four units the side...

Page 15: ...HT 1321 2122 ht 300 MINI VOIR NOTICE D INSTALLATION REFER TO INSTALLATION MANUAL Unit with grille protection option 3 7 Multiple unit installation Solid wall Solid wall NOTE If the walls are higher th...

Page 16: ...ter side operating pressure plus hydraulic module kPa 400 400 400 400 400 400 Fans Axial with rotating shroud Quantity 1 1 1 1 2 2 Maximum total air flow l s 3748 3736 4035 4036 7479 8072 Max speed st...

Page 17: ...pressor I Nom I Max I Max LRA 1 LRA 2 Cosine 080 100 120 150 200 300 Un Un 10 A A phi max ZH24KVE 13 6 18 3 20 3 99 51 0 85 1 ZH33KVE 17 3 24 2 26 9 127 66 0 85 1 2 ZH40KVE 20 4 30 0 33 2 167 87 0 89...

Page 18: ...of the machines The operating environment for the TD units is specified below 1 Environment 1 Environment as classified in EN 60721 corresponds to IEC 60721 outdoor installation 1 ambient temperature...

Page 19: ...1 120 3 8 3 8 150 4 6 4 6 200 5 9 6 4 300 6 1 8 5 1 Maximum flow rate at an available pressure of 20 kPa minimum 2 Maximum flow rate at a water temperature difference of 3K in the plate heat exchanger...

Page 20: ...hieve this volume it may be necessary to add a storage tank to the circuit This tank should be equipped with baffles to allow mixing of the fluid water or brine Please refer to the examples below Bad...

Page 21: ...llation practises for units installed outside have been applied in accordance with IEC 60364 table 52C No 17 suspended aerial lines No 61 buried conduit with a derating coefficient of 20 The calculati...

Page 22: ...able wire Max connectable section Min wire section Max wire section Section mm2 Section mm2 Max length m Wire type Section mm2 Max length m Wire type 080 1 x 10 1 x 6 100 XLPE Cu 1 x 10 245 PVC Cu 100...

Page 23: ...he disturbance of the oxygenation conditions encou rages destabilisation of copper hydroxides and enlarge ment of particles Electric conductivity 10 600 S cm pH Ideal case pH neutral at 20 25 C 7 5 pH...

Page 24: ...sed Open It is recomended to use a primary glycol loop for low temperature applications as shown below 2 1 3 Water network Unit Legend B Primary glycol loop minimum 10 C Intermediate heat exchanger D...

Page 25: ...e information for the pump inlet see Control manual I Temperature sensor Note Provides temperature information for the water type heat exchanger outlet see Control manual J Temperature sensor Note Pro...

Page 26: ...he heat exchanger leaving piping F Shut off valve G Available pressure pump H Temperature probe BPHE inlet Note Gives heat exchanger entering temperature information see installation manual I Pressure...

Page 27: ...hydraulic circuit presence of solid contaminants Take another reading Compare this value to the initial value If the pressure drop has decreased this indicates that the screen filter must be removed...

Page 28: ...units are given for the higher variable speed of the pump maximum available pressure Data applicable for Fresh water 20 C In case of use of the glycol the maximum water flow is reduced For pure water...

Page 29: ...standard configuration It can also be located in the leaving water In this case two additional sensors must be added on the common piping All parameters required for the master slave function must be...

Page 30: ...ctivated after a shut down of the heat pump following a fault condition safety device This requires only a 400 V 3 ph 50 Hz power supply source For the required configuration of the stages consult the...

Page 31: ...um energy efficiency Pa 90 195 Nominal speed rpm 710 966 Specific ratio 1 002 1 002 Relevant information to facilitate the disassembly recycling or removal of the product at the end of life See servic...

Page 32: ...matically reset high pressure safety switches calibrated to 3130 kPa relative pressure soft alarm is manually reset NOTES Monitoring during operation Follow the regulations on monitoring pressurised e...

Page 33: ...time equalisation Lon gateway Two directional communication board complying with Lon Talk protocol Connects the unit by communication bus to a building management system Bacnet over IP Two directiona...

Page 34: ...2 Applicable rules for units incorporated into an air duct system Ensure that the suction or discharge inlets are not accidentally obstructed by the panel positioning e g low return or open doors etc...

Page 35: ...the electrical protection devices Check the correct operation of all heaters Replace the fuses every 3 years or every 15000 hours age hardening Check that no water has penetrated into the control box...

Page 36: ...ump if service considerations allow this Clean evaporators guarantee optimal operation of your unit Cleaning is necessary when the evaporators begin to become fouled The frequency of cleaning depends...

Page 37: ...4 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 15 36 46 41 64 24 5 56 46 60 8 5 75 5 4 11 5 15 25 37 08 42 24 24 75 56 9 61 22 6 6 57 12 65 15 5 37 7...

Page 38: ...pected for crossed wires All plug assemblies are tight Check air handling systems All air handlers are operating All water valves are open All fluid piping is connected properly All air has been vente...

Page 39: ...tion of l s Carry out the QUICK TEST function see Aquaciat Cal o TD Connect Touch control manual Check and log on to the user menu configuration Load sequence selection Capacity ramp loading selection...

Page 40: ...ce Printed in the European Union Manufacturer reserves the right to change any product specifications without notice CARRIER participates in the ECP programme for LCP HP Check ongoing validity of cert...

Reviews: