CIAT AQUACIAT CALEO CONNECT TOUCH Instruction Manual Download Page 24

7  -  STANDARD CONTROL OPERATIONS AND OPTIONS

7.5  Control point

The control point represents the water temperature that the unit 
must produce. The control point calculation is based on the active 
setpoint and its reset. 

control point = active se reset

7.5.1  Active setpoint

The control can manage two heating setpoints. The 

first heating 

setpoint

 is normally used during occupied periods, whereas the 

second heating setpoint 

is used during unoccupied periods.

Depending on the current operating type, the active setpoint can 
be selected:

• 

By choosing the active setpoint in the General Parameters 
menu (Setpoint Select, GENUNIT).

•  Via the volt-free contacts (see section 3.7).
• 

Via network commands [SP_SEL].

• 

Via the schedule setting – schedule 2 (OCCPC02S). 

 

See also section 5.9

Mode

Setpoint control

Local

Regardless of the current setpoint schedule, the user can select the 

setpoint manually via the control interface (Setpoint Select, GENUNIT).

Remote

If the setpoint switch is used once, the setpoint schedule control 

will be cancelled (setpoint control will be based on setpoint switch 

selection only).

Network

Regardless of the current setpoint schedule, the user can select the 

setpoint manually via the control interface (Setpoint Select, GENUNIT) 

or the service tool. Once the forced selection is deactivated, the setpoint 

schedule will be used again.

The following tables summarise the possible setpoint selections 
based on the control type (local, remote, network) and the following 
parameters:

• 

Setpoint select.

• 

Setpoint selection contact status.

• 

Schedule 2 status for setpoint selection.

Local operating type
Setpoint Select 

[SP_SEL]

Setpoint occupancy 

[SP_OCC]

Active setpoint

1

sp 1

-

heating setpoint 1

2

sp 2

-

heating setpoint 2

0

auto 

occupied

heating setpoint 1

0

auto 

unoccupied

heating setpoint 2

Remote operating type
Remote Setpoint Switch [SETP_SW]

Active setpoint

open

heating setpoint 1

closed

heating setpoint 2

Network operating type
Setpoint Select 

[SP_SEL]

Setpoint occupancy 

[SP_OCC]

Active setpoint

0

auto 

occupied

heating setpoint 1

0

auto 

unoccupied

heating setpoint 2

7.5.2  Reset

Reset  means  that  the  active  control  point  is  modified  so  that 

the machine capacity required is adjusted to be as close as 
possible to the demand. 

The reset source can be provided by one of the following:

•  Outdoor air temperature that gives a measure of the load 

trends for the building. When the outdoor air temperature 
increases, the heating demand normally decreases and the 
active setpoint will be decreased thanks to the applied reset.  

•  Return water temperature

 (heat exchanger ΔT gives an 

average building load). Delta T (ΔT) is the difference 
between leaving and entering fluid temperatures (LWT minus 

EWT). When the load is light, temperature difference across 

the exchanger will be relatively small. The reset value should 
be configured by the user and its configuration may differ 
depending on the size of the water exchanger.

•  4-20 mA reset signal provided by an active sensor 

connected to the input: If the reading of the 4-20 mA signal/

external temperature value increases (load is lighter), then 

the current setpoint will be lowered.

In response to a change in the outside air temperature, Delta T, 
or 4-20 mA reset signal reading, the control point is reset in order 

to optimise unit performance. The source of the reset (OAT, ΔT, 
4-20 mA signal) can be configured by the user. 

To set the source of the reset

1. Navigate to the Configuration menu.
2. Select 

Heat/Cool Config

 (HCCONFIG).

3. Set 

Heating Reset Select

 [hr_sel].

Heating Reset Select [hr_sel]
0 = none                   

1 = OAT                   

2 = delta T

  

3 = 4-20mA

Reset is a linear interpolation function based on the following 

three parameters:

•  A reference at which reset is zero (no reset value). 
• 

A reference at which reset is maximum

 (full reset value). 

• 

The maximum possible reset value:

 The difference between 

the lowest reset value (no reset value) and the highest 
possible reset value (full reset value). “Heating Reset Deg. 

Value” [hr_deg] represents the maximum possible reset. 

Reset source

No reset parameter

Full reset parameter

OAT

oathr_no 

oathr_fu

delta T (ΔT) 

dt_hr_no 

dt_hr_fu

4-20 mA signal

I_hr_no 

I_hr_fu

-20°C

Reset based on OAT

+10°C

0 K

Reset based on delta T

3 K

4 mA

Reset based on analogue input

20 mA

no reset

selection

full reset

 Legend:

A: Maximum reset value

B: OAT / delta T / 4-20 mA for no reset

C: OAT / delta T / 4-20 mA for full reset

D: Building load

Reset value [°C]

Building load [

%]

Reset example in Heating mode

 

AQUACIAT

CALEO

 

 EN - 22

 

Summary of Contents for AQUACIAT CALEO CONNECT TOUCH

Page 1: ...Instruction manual AQUACIAT CALEO 14 300 02 2018 10199 CONNECT TOUCH...

Page 2: ...he user interface provided in this manual include text in English After changing the language of the system all labels will be in the language selected by the user Please read all instructions prior t...

Page 3: ...ouch buttons 5 4 4 Menu structure 6 5 SETTING UP CONNECT TOUCH CONTROL 7 5 1 General description 7 5 2 Welcome screen 7 5 3 Synoptic screen 7 5 4 Unit start stop 7 5 5 Display settings 8 5 6 Main menu...

Page 4: ...power source RISK OF BURNS Electrical currents may cause components to get hot Handle the power cable electrical cables and conduits terminal box covers and motor frames with great care 2 1 Control sy...

Page 5: ...d to monitor the water pressure The pump is protected against cavitation low pump entering pressure 3 5 Temperature sensors Temperature sensors constantly measure the temperature of various components...

Page 6: ...sed to control the pump and unit operation open pump continues to run closed pump is stopped unit is not allowed to start DHW Tank Request Switch SIOB DI 06 63 64 Used to command the domestic hot wate...

Page 7: ...ernet connector 3 Modbus RS485 connector 4 Internal bus RS485 5 Power supply connector 24 VAC This RS 485 bus can be used as a second internal bus for the connection of gateway If it is the case then...

Page 8: ...Configuration User Configuration Pump Configuration Date Time 0 10V Pump Config Heat Cool Config Control Identification Schedule Configuration menu Main menu ModbusRTU Config ModbusTCP IP Config Netwo...

Page 9: ...ng the table content ACCESS DENIED Equipment controller denies access to one of the tables LIMIT EXCEEDED The value entered exceeds the parameter limit Save changes Modifications have been made The ex...

Page 10: ...tem allows users to add new languages to the control To learn more about language customization please contact your local service representative 5 5 2 System of measurement The control offers the poss...

Page 11: ...modifiable parameters such as pump configuration schedule menu etc The Configuration menu is password protected To access the Configuration menu press the Main menu button located in the upper left pa...

Page 12: ...HEDULE 3 Go to OCCPC01S 4 Select appropriate check boxes to set the unit occupancy on specific days 5 Define the time of occupancy 6 When the time schedule is set the selected period will be presented...

Page 13: ...the unit cannot be started stopped via the web interface All other operations including monitoring unit parameters or unit configuration can be performed via the web browser interface 5 10 2 Web brow...

Page 14: ...t selection 5 0 Auto 1 Spt1 2 Spt2 0 Auto schedule control 1 Heating setpoint 1 2 Heating setpoint 2 6 SP_OCC no yes Setpoint Occupied Setpoint occupancy status 7 CHIL_S_S disable enable Net Cmd Start...

Page 15: ...kPa Eco Suction Pressure Economizer suction pressure 4 5 INTERNAL HYDRONIC MODULE Internal hydronic module 6 W_P_IN kPa Inlet Water Pressure Inlet water pressure Displayed in French by default Setpoi...

Page 16: ...utput 17 ALARM off on Alarm Relay Status Alarm relay status 18 RUNNING off on Running Relay Status Running relay status 19 DHW_3WV off on DHW 3 Way Water Valve DHW 3 way water valve Displayed in Frenc...

Page 17: ...splayed in French by default Domestic Hot Water Menu DHW_STAT No Name Status Default Unit Displayed text Description 1 dhw_mode 0 to 2 Mode Mode 2 0 SHC 1 DHW 2 AntiLeg 0 Space Heating Control SHC 1 D...

Page 18: ...de additional features some tables may contain parameters that cannot be configured for a given unit General Config Menu GENCONF No Name Status Default Unit Displayed text Description 1 ramp_sel no ye...

Page 19: ...set Value OAT max reset value 3 dt_hr_no 0 to 14 0 K Delta T No Reset Value Delta T no reset value 4 dt_hr_fu 0 to 14 0 K Delta T Full Reset Value Delta T max reset value 5 I_hr_no 0 to 20 0 mA Curren...

Page 20: ...tware version 4 xx chars MAC address Serial Number Serial number MAC address Displayed in French by default 0 10V Pump Config Menu FLOWCONF No Name Status Default Unit Displayed text Description 1 log...

Page 21: ...Parity High 4 Force Parity High 17 stop_bit 0 to 1 0 Stop bit Stop bit 18 0 One Stop Bit 0 One Stop Bit 19 1 two Stop Bits 1 Two Stop Bits 20 real_typ 0 to 1 1 Real type management Real type managemen...

Page 22: ...y can never exceed the limit setpoint activated by these contacts The limit setpoints can be modified in the SETPOINT menu By setting DEM_LIM when the unit is in Network mode By lag limit set by the m...

Page 23: ...d through the LEN drive The status of the internal pump is displayed in the Pump Status menu under Drive pump status External Pump Output PUMP_EXT Pump Status menu and External Pump Output PUMP_EXT Ou...

Page 24: ...trol point is modified so that the machine capacity required is adjusted to be as close as possible to the demand The reset source can be provided by one of the following Outdoor air temperature that...

Page 25: ...ng mode if at least one of the following conditions applies The volt free tank request contact is open The maximum operating time for the DHW mode has elapsed Time schedule 3 is in an unoccupied perio...

Page 26: ...eating stage will not be used even if the heating demand cannot be satisfied This electric heating backup option can be enabled by setting 1 Elec Stage For Backup ehs_back to yes in the Heat Cool Conf...

Page 27: ...ory Basic Reset Alarms User 8 2 Displaying current alarms The Current alarms menu may display up to 10 current alarms To access the list of currently active alarms 1 Press the Alarm button in the uppe...

Page 28: ...e 15 4901 Loss of communication with SIOB Board Number A Bus installation fault communication error Unit shuts down Automatic if communication is re established 16 4601 Loss of communication with AUX1...

Page 29: ...company Maintenance date passed No action alert Automatic if the new maintenance date is set 37 8000 Initial Factory Configuration Required No factory configuration Unit cannot be started Automatic if...

Page 30: ...ed increase Contact Manufacturer Agency 38 over current during product speed decrease Contact Manufacturer Agency 39 over current during product speed hold Contact Manufacturer Agency 41 drive type er...

Page 31: ...erious damage can occur to your equipment TheManufacturerprovidesawiderangeofservicecontractswhich embrace the assistance of highly qualified HVAC engineering professionals ready to help if needed The...

Page 32: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Reviews: