L
N
3
4
5
6
7
8
9
10
11
12
13
14
15
16
L
CF
SA
E / I
RDC
GND
V HEAT
V COOL
V FAN
Various settings are possible with this type of thermostat. Read the
installation manual carefully before installation. For proper operation,
please check the parameters below and adjust if necessary:
P01: 2 (system type)
P02: 0 or 1 (1 = automatic change-over heat/cool)
C14: 30 % (minimum fan speed when the electric heater is
switched on) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **
*
With the Comfort Line and the Major Line with ducting: check
minimum airflow, see installation manual of the relevant unit.
** With the Comfort Line and the Major Line with ducting: the capacity (air
volume) depends on the resistance in the duct and the grilles. In
most cases, the maximum speed should be set between 5V and 8V.
Explanations:
E/I = N/A *
RDC =
Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit
*
The functions of these outputs can be changed with parameters C17,
C18 en C19. See for more information the installation manual.
**
Use a separate shielded cable (see for more information the
installation manual)
Ph
N
Ph
7
6
V1
V2
Ph
Ph
6
C
PE
N
Ph
N
L
JP1
1TB
TB
1TB
XB
XB
XB
XB
SM
99DA-SEI-EC01
PE
A1F / X2
3
8
5
15
A+
A-
5
5
12
10
PE
N
L
14
Major
Line
Melody 2
Coadis
Line
XB
XB
XB
Ph
N
Ph
7
Ph
Ph
6
C
PE
N
Ph
Ph
N
Ph
7
V1
V2
Ph
Ph
6
C
PE
N
Ph
XB
XB
XB
XB
Comfort
Line
6
+
-
6
NOTE: Check whether the unit is
suitable for 0-10V control of the
fan motor
POWER SUPPLY 230V~
2-PIPE FAN COIL UNITS WITH ELECTRIC HEATER(S)
APPLICATION
Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V
– on/off
REMARKS
1: All electrical connections must be made in accordance with the local regulations
2: ---------- External cables (not supplied by CIAT)
3:
Minimum cable diameter 1,5 mm
2
(230V~)
4:
Use shielded cable for 0-10V signal cable of the fan motor
5:
For other connections/information, see the electrical wiring diagram of the relevant unit
Controlbox on the motor
Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump
Remark 4
18-05-2022