Various settings are possible with this type of thermostat. Read the 
installation manual carefully before installation. For proper operation, 
please check the parameters below and adjust if necessary:

P01: 0 (system type)
P02: 1 (manual change-over heat/cool) *
C15: 2 V (minimum fan speed)
C16: Maximum fan speed (V) **

*

Heating or cooling modes are selected by keeping the           button
depressed for some seconds, until the display shows one of the 
following texts which indicates the current mode:
HEA : Heating mode
COO : Cooling mode
Then, by pressing the arrow keys, the user can change the desired 
operating mode.

**

With the Comfort Line and the Major Line with ducting: the capacity (air 
volume) depends on the resistance in the duct and the grilles. In 
most cases, the maximum speed should be set between 5V and 8V.

Explanations:

E/I = Change-over contact heating/cooling *
RDC = Contact to activate the “Economy” function (set P18) *
SM = Supply water sensor **
SA = Room sensor (if applied P11 = 1) **
CF = Window contact * and **
XB, TB, A1F / X2 = terminals fan coil unit

The functions of these outputs can be changed with parameters C17, 
C18 en C19. See for more information the installation manual.

**

Use a separate shielded cable (see for more information the 
installation manual)

Melody 2

POWER SUPPLY 230V~

Ph

N

Ph

6

+

-

Ph

Ph

6

C

PE

N

Ph

NOTE: Check whether the unit is 

suitable for 0-10V control of the 

fan motor

2-PIPE FAN COIL UNITS

APPLICATION

Thermostat type: 99DA-SEI-EC01
Fan coil units with EC fan (HEE): 0-10V control
Actuators of the 2- or 3-way valves: 230V 

– on/off

REMARKS

1:  All electrical connections must be made in accordance with the local regulations
2:  ---------- External cables (not supplied by CIAT)
3:

Minimum cable diameter 1,5 mm

2

(230V~)

4:

Use shielded cable for 0-10V signal cable of the fan motor

5:

For other connections/information, see the electrical wiring diagram of the relevant unit

Coadis Line 600
6 = w/o condensate pump
12 = with condensate pump

Remark 4

18-05-2022