Chromalox MWS 300-600 kW Installation & Operation Manual Download Page 5

5

Expansion Tank Installation

Mount the expansion tank so it is the highest point in 

the system and if possible at least 15 feet (5m) above 

the height of the pump. Connect the fluid level sight 

glass to the expansion tank. To safeguard employees 

and equipment, run the vent line either out of the build-

ing or down into a 55 gallon drum. The vent line piping 

should match the port size on the expansion tank.

To avoid possible rupture of expansion tank 

due to pressure, vent line should be checked 

on a regular basis to be sure it is always open 

to the atmosphere. Failure to do so may result 

in rupture of the expansion tank or other parts 

of the system causing injury or hazard.

Note: If the expansion tank cannot be mounted above 

the highest point in the system, or if the system is going 

to operate above the boiling temperature of the heat 

transfer fluid, the expansion tank will have to be pres-

surized. This eliminates the possibility of heat transfer 

fluid flashing into vapor in the heater, at the point of 

high velocity in the system, at the suction of the pump 

or causing the pump to vapor lock due to insufficient 

NPSH (net positive suction head). This pressure should 

be 5-10 PSI (0.34 - 0.69 bar) above the vapor pressure 

of the heat transfer fluid at its operating temperature.

If expansion tank is to be pressurized, then it 

must be equipped with safety relief valve(s). If 

this pressure exceeds 15 PSIG, then the heat 

transfer system and expansion tank should be 

ASME certified.

DO NOT mount expansion tank directly on top of 

system 

unless absolutely necessary. If mounted on 

system, provisions must be made for cooling of the 

expansion tank line. Maximum safe operating tempera-

tures are reduced when expansion tank is mounted on 

system unless positive suction pressure of 2 to 3 psig 

(0.14-0.21 bar) is maintained on pump.

Pump Motor

The pump/motor is a close-coupled centrifugal pump 

rated for 300˚F (149˚C). Pump and motor mounts should 

be checked and tightened if loosened during shipment.
DO provide for expansion and contraction of process 

piping and connections to the system. Piping strains 

can cause pump and motor misalignment, excessive 

wear on pump body, bearings and stuffing box packing 

or mechanical seal and will eventually cause failure of 

the pump and system.
Piping should be properly supported so pump can be 

removed without changing the position of the piping. 

If piping moves when the pump is removed, pump 

malfunction is probably due to stresses and twisting 

caused by the piping. These stresses will multiply when 

the system is hot due to thermal expansion.
Refer to graphs for pump performance curves.

50-150 kW Unit (3 hp)

18

PER HOUR

CUBIC METERS

4

9

14

U.S.  GALLONS

PER  MINUTE

6

9

12 17

20

40

18 26

24

30

35

43

60

80

100

37 52

43 61

120

140

20

40

60

80

27

22

120

100

60 Hz

MTRS

TOTAL HEAD

PSI FEET

3500  RPM

70°F

1.0 S.G.

20

10

0

N

P

S

H

R  

F

E

E

T

0

0

NPSH REQ.

5.25

50 55 60 65

70

70

65

60

3 HP

Summary of Contents for MWS 300-600 kW

Page 1: ...1 Installation Operation Manual MWS Series Water Water Glycol System PQ449 2 161 123417 033 June 2019 ...

Page 2: ...les 50 thru 600kW In hazardous areas pipe surfaces could achieve temperatures high enough to cause auto ignition of the hazardous material pres ent Consult Article 500 of the National Elec tric Code for further information on the maxi mum allowable temperature for a specific application Unit Proportions Unit Size Dry Weight Lbs Width In Depth In Height1 In Flow Rate2 GPM Pressure2 TDH Ft Motor HP ...

Page 3: ...ion and bolted down 1 Allow at least 1 foot or more around unit for proper maintenance 2 Unit is designed for 104 F 40 C maximum operat ing environment 3 Unit will be operating at elevated temperatures Proper care must be provided to ensure personnel safety Piping Installation 1 The pipe size should be the same as the system piping connections All piping must be supported so the pump is not carryi...

Page 4: ... Repair leaks and replace soaked insulation immediately Relief Valve Installation The MWS can be operated with water and glycol wa ter liquid combinations Varying combinations of fluid produce different boiling points and various pressures See Tables 1 and 2 as examples Table 1 100 Water Temp F Pressure PSI Temp C Pressure bar 200 0 93 0 220 3 104 0 21 240 10 116 0 69 260 21 127 1 45 280 35 138 2 ...

Page 5: ...y relief valve s If this pressure exceeds 15 PSIG then the heat transfer system and expansion tank should be ASME certified DO NOT mount expansion tank directly on top of system unless absolutely necessary If mounted on system provisions must be made for cooling of the expansion tank line Maximum safe operating tempera tures are reduced when expansion tank is mounted on system unless positive suct...

Page 6: ...ET 3500 RPM 70 F 1 0 S G 15 10 5 N P S H R F E E T 0 0 NPSH REQ 5 38 20 45 50 60 65 70 72 70 65 60 50 5 HP 45 PER HOUR CUBIC METERS 11 22 34 U S GALLONS PER MINUTE 6 12 9 17 18 26 20 40 60 24 35 30 37 43 52 80 100 120 43 61 49 69 140 160 50 100 150 200 68 56 300 250 60 Hz MTRS TOTAL HEAD PSI 55 78 FEET 180 3500 RPM 70 F 1 0 S G 30 20 10 0 N P S H R F E E T 350 79 0 0 NPSH REQ 5 50 60 65 70 72 76 7...

Page 7: ... of the wire 5 The unit is completely wired The only wiring nec essary is to terminals L1 L2 and L3 in the control panel and the ground lug in the control panel ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property damage Heater must be installed or serviced by a qualified person in accordance with the National...

Page 8: ...ocess closed when the fluid reaches them The fill line remains open until the expansion tank sight glass indicates being 1 3 full After the system is filled shut down the pump and close the fill valve Open system inlet valve 6 Turn master circuit breaker off Bleed air from all lines including one located above pump and re close all bleed valves 7 The temperature limiting device located inside the ...

Page 9: ... provided with optional equipment that require additional installation concerns Strainer Inlet Outlet Valves and Dedicated Fill Connections Ordering 2 or more of these options will require on site installation to avoid shipment damage The order of assembly starting at pump inlet should be strainer fill connection then gate valve A bolting kit with gas kets is provided for simple installation Pleas...

Page 10: ...00 443 2640 Maximum Temperatures DO NOT attempt to operate any heat transfer system at temperatures higher than those recommended by the manufacturer Chromalox heat transfer systems are designed for a particular maximum temperature If you do not know this design temperature check with the Chromalox factory Exceeding the designed temperature of the heat transfer system will void the warranty Exceed...

Page 11: ...ipment Check piping and flange alignment retighten and torque all bolts to specifications H System leaks at temperature and after cool down Expansion and contraction due to temperature has loosened connec tions Check all flange bolts and connections retighten and torque to manufacturer s specifications Wrong gasket materials Replace gaskets as necessary I Insufficient suction pressure 0 or vacuum ...

Page 12: ...ocouple 048419 018 Relief Valve For Replacement Heater Bundle or spare parts not listed here please contact Chromalox Service Center 1 800 443 2640 2014 Chromalox Inc Limited Warranty Please refer to the Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx Chromalox Inc 2150 N Rulon White Blvd Ogden UT 84404 800 368 2493 www chr...

Reviews: