Chromalox MWS 300-600 kW Installation & Operation Manual Download Page 3

3

This system is NOT for use with oil based or 

synthetic heat transfer fluids. 

To avoid possible damage to the heaters do not 

energize the heater unless the system is filled 

with fluid.

EXPLOSION HAZARD. When heating in closed 

vessels, controls and back-up controls must be 

used to regulate build-up of temperature and/

or pressure. 

Read manufacturer’s technical bulletins and instruc-

tions carefully. 
If you are not sure you are using an accepted heat 

transfer fluid, check with fluid manufacturer.

FIRE/EXPOSION HAZARD. This heater is not 

intended for use in hazardous atmospheres 

where flammable vapors, gases, liquids or 

other combustible atmospheres are present as 

defined in the National Electrical Code. Failure 

to comply can result in personal injury or prop-

erty damage. 

DO NOT mix heat transfer fluids unless authorized and 

approved by the fluid manufacturer. All heat transfer 

fluids are not compatible with each other, whether 

made by the same manufacturer or a different manu-

facturer. If you plan to switch fluids, check with the fluid 

manufacturer to determine the following.
A.  Is the new fluid compatible with the old?
B.  What is the recommended cleaning method to re-

move the old fluid, its sludge, or any deposits re-

maining in the system?

C.  Does the fluid manufacturer have a reclaiming ser-

vice for used fluid? Do they have recommended 

procedure for disposal of used or old fluid?

DO NOT allow heat transfer fluid to reach freezing tem-

peratures, as this can permanently damage system.

Fluid Compatibility

Unit Installation

Note: When installing system, allow sufficient room to 

remove heating bundle. 

Hydraulics
Note:
 The MWS systems should be mounted so the 

control box does not fall in direct sunlight.
The bed plate should be mounted on a level, solid 

foundation and bolted down.

1.  Allow at least 1 foot or more around unit for proper 

maintenance,

2.  Unit is designed for 104˚F (40˚C) maximum operat-

ing environment.

3.  Unit will be operating at elevated temperatures. 

Proper care must be provided to ensure personnel 

safety.

Piping Installation

1.  The pipe size should be the same as the system 

piping connections. All piping must be supported 

so the pump is not carrying any of the pipe weight. 

If these instructions are not followed, distortion in 

the pump may cause unnecessary wear and faulty 

operation.

2.  The piping of the entire system should be arranged 

to minimize pockets where air may be trapped. 

Manual air vents or bleeder valves should be pro-

vided in the system where air pockets may occur, 

or where the flow of fluid may drop.

3.  Piping should be properly supported so pump can be 

removed without changing the position of the piping. 

If piping moves when the pump is removed, pump 

malfunction is probably due to stresses and twist-

ing caused by the piping. These stresses will multiply 

where the system is hot due to thermal expansion.

4.  If there is a high differential pressure between the 

inlet and outlet of the heat transfer system at oper-

ating temperature, this is probably due to a piping 

restriction. A continuing high differential pressure 

can cause excessive wear on the pump and pump 

stuffing box packing or mechanical seal and will 

eventually cause premature failure of the pump. 

The major causes of restrictions are:

 

a. Inlet and outlet pipes smaller than provided on 

the system.

 

b. Piping many processes in series with one another. 

To reduce the pressure drop of the system, equip-

ment should be re-piped in balanced parallel flow.

DO provide for expansion and contraction of process 

piping and connections to the system. Piping strains 

can cause pump and motor misalignment, excessive 

wear on pump body, bearings and stuffing box packing 

or mechanical seal and will eventually cause failure of 

the pump and system.

Summary of Contents for MWS 300-600 kW

Page 1: ...1 Installation Operation Manual MWS Series Water Water Glycol System PQ449 2 161 123417 033 June 2019 ...

Page 2: ...les 50 thru 600kW In hazardous areas pipe surfaces could achieve temperatures high enough to cause auto ignition of the hazardous material pres ent Consult Article 500 of the National Elec tric Code for further information on the maxi mum allowable temperature for a specific application Unit Proportions Unit Size Dry Weight Lbs Width In Depth In Height1 In Flow Rate2 GPM Pressure2 TDH Ft Motor HP ...

Page 3: ...ion and bolted down 1 Allow at least 1 foot or more around unit for proper maintenance 2 Unit is designed for 104 F 40 C maximum operat ing environment 3 Unit will be operating at elevated temperatures Proper care must be provided to ensure personnel safety Piping Installation 1 The pipe size should be the same as the system piping connections All piping must be supported so the pump is not carryi...

Page 4: ... Repair leaks and replace soaked insulation immediately Relief Valve Installation The MWS can be operated with water and glycol wa ter liquid combinations Varying combinations of fluid produce different boiling points and various pressures See Tables 1 and 2 as examples Table 1 100 Water Temp F Pressure PSI Temp C Pressure bar 200 0 93 0 220 3 104 0 21 240 10 116 0 69 260 21 127 1 45 280 35 138 2 ...

Page 5: ...y relief valve s If this pressure exceeds 15 PSIG then the heat transfer system and expansion tank should be ASME certified DO NOT mount expansion tank directly on top of system unless absolutely necessary If mounted on system provisions must be made for cooling of the expansion tank line Maximum safe operating tempera tures are reduced when expansion tank is mounted on system unless positive suct...

Page 6: ...ET 3500 RPM 70 F 1 0 S G 15 10 5 N P S H R F E E T 0 0 NPSH REQ 5 38 20 45 50 60 65 70 72 70 65 60 50 5 HP 45 PER HOUR CUBIC METERS 11 22 34 U S GALLONS PER MINUTE 6 12 9 17 18 26 20 40 60 24 35 30 37 43 52 80 100 120 43 61 49 69 140 160 50 100 150 200 68 56 300 250 60 Hz MTRS TOTAL HEAD PSI 55 78 FEET 180 3500 RPM 70 F 1 0 S G 30 20 10 0 N P S H R F E E T 350 79 0 0 NPSH REQ 5 50 60 65 70 72 76 7...

Page 7: ... of the wire 5 The unit is completely wired The only wiring nec essary is to terminals L1 L2 and L3 in the control panel and the ground lug in the control panel ELECTRIC SHOCK HAZARD Disconnect all power before installing or servicing heater Failure to do so could result in personal injury or property damage Heater must be installed or serviced by a qualified person in accordance with the National...

Page 8: ...ocess closed when the fluid reaches them The fill line remains open until the expansion tank sight glass indicates being 1 3 full After the system is filled shut down the pump and close the fill valve Open system inlet valve 6 Turn master circuit breaker off Bleed air from all lines including one located above pump and re close all bleed valves 7 The temperature limiting device located inside the ...

Page 9: ... provided with optional equipment that require additional installation concerns Strainer Inlet Outlet Valves and Dedicated Fill Connections Ordering 2 or more of these options will require on site installation to avoid shipment damage The order of assembly starting at pump inlet should be strainer fill connection then gate valve A bolting kit with gas kets is provided for simple installation Pleas...

Page 10: ...00 443 2640 Maximum Temperatures DO NOT attempt to operate any heat transfer system at temperatures higher than those recommended by the manufacturer Chromalox heat transfer systems are designed for a particular maximum temperature If you do not know this design temperature check with the Chromalox factory Exceeding the designed temperature of the heat transfer system will void the warranty Exceed...

Page 11: ...ipment Check piping and flange alignment retighten and torque all bolts to specifications H System leaks at temperature and after cool down Expansion and contraction due to temperature has loosened connec tions Check all flange bolts and connections retighten and torque to manufacturer s specifications Wrong gasket materials Replace gaskets as necessary I Insufficient suction pressure 0 or vacuum ...

Page 12: ...ocouple 048419 018 Relief Valve For Replacement Heater Bundle or spare parts not listed here please contact Chromalox Service Center 1 800 443 2640 2014 Chromalox Inc Limited Warranty Please refer to the Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx Chromalox Inc 2150 N Rulon White Blvd Ogden UT 84404 800 368 2493 www chr...

Reviews: