8
Operation
Process temperature should never exceed
maximum system rating.
For complete process controller instructions, please
refer to Chromalox manual PK510.
If needed, factory settings for process controller can be
referenced per table below:
Unit
Drawing Number
600˚F, Contactor
223-123625-213
600˚F, SCR Trim
223-123625-215
650˚F, Contactor
223-123625-214
650˚F, SCR Trim
223-123625-216
Element overtemperature control is pre-set from the
factory at 500˚F (260˚C). This should be adjusted to a
range of 50-100˚F (28-56˚C) above the operating set-
point. For complete overtemperature controller instruc-
tions, please refer to Chromalox manual PDS LIMIT.
Chromalox MoS unit is a component to a cus-
tomer integrated process. Ensure adequate
safety devices have been installed and func-
tion properly. Ensure proper review of Control
Panel Information Package for proper installa-
tion and use.
Optional Accessories
Some MOS units are provided with optional equipment
that require additional installation concerns.
Strainer, Inlet/Outlet Valves and Dedicated
Fill Connections
Ordering (2) or more of these options will require on-
site installation to avoid shipment damage. The order
of assembly, starting at pump inlet should be: gate
valves, strainer then fill connections. A bolting kit, with
gaskets is provided for simple installation. Please note
that during operation, the strainer should be checked
as part of a regular maintenance program.
All added-on equipment must be adequately support-
ed to avoid damage to pump.
Purge Connections
Nitrogen purge connections are provided for a hazard-
ous area. Ensure nitrogen system is operational and
installed correctly prior to operation. Incoming power
wiring must also be installed in accordance with NEC
requirements for hazardous area.
Digital Overtemperature Control
The overtemperature controller is pre-set at the fac-
tory to 500˚F (260˚C). The controller should be set for
50-100˚F (28-56˚C) higher than operating temperature.
Please refer to Chromalox manual PK508 for complete
operation.
Strainer
Fill Connection
Note: All piping add-on accessories must be adequately supported to avoid damage to pump.
Inlet / Outlet
Gate Valves
Figure 2 Optional Piping Accessory Assembly