Chromalox MOS Series Installation & Operation Manual Download Page 3

3

Fluid Compatibility

This system is NoT for use with water, ethylene 

glycol and water mixture or some of the syn-

thetic heat transfer fluids. 

To avoid possible damage to the heaters do not 

energize the heater unless the system is filled 

with fluid.

Read manufacturer’s technical bulletins and instruc-

tions carefully. Some heat transfer fluids may ignite or 

burn spontaneously if not properly used.
If you are not sure you are using an accepted heat 

transfer fluid, check with fluid manufacturer.

DO NOT mix heat transfer fluids unless authorized and 

approved by the fluid manufacturer. All heat transfer 

fluids are not compatible with each other, whether 

made by the same manufacturer or a different manu-

facturer. If you plan to switch fluids, check with the fluid 

manufacturer to determine the following.
A.  Is the new fluid compatible with the old?
B.  What is the recommended cleaning method to re-

move the old fluid, its sludge, or any deposits re-

maining in the system?

C.  Does the fluid manufacturer have a reclaiming ser-

vice for used fluid? Do they have recommended 

procedure for disposal of used or old fluid?

Unit Installation

Note: When installing system, allow sufficient room to 

remove heating bundle. 

Hydraulics
Note:
 The MOS systems should be mounted so the 

control box does not fall in direct sunlight.
The bed plate should be mounted on a level, solid 

foundation and bolted down.

1.  Allow at least 1 foot or more around unit for proper 

maintenance,

2.  Unit is designed for 104˚F (40˚C) maximum operat-

ing environment.

3.  Unit will be operating at elevated temperatures. 

Proper care must be provided to ensure personnel 

safety.

Piping Installation

1.  The pipe size should be the same as the system 

piping connections. All piping must be supported 

so the pump is not carrying any of the pipe weight. 

If these instructions are not followed, distortion in 

the pump may cause unnecessary wear and faulty 

operation.

2.  The piping of the entire system should be arranged 

to minimize pockets where air may be trapped. 

Manual air vents or bleeder valves should be pro-

vided in the system where air pockets may occur, 

or where the flow of fluid may drop.

3.  Piping should be properly supported so pump can 

be removed without changing the position of the 

piping. If piping moves when the pump is removed, 

pump malfunction is probably due to stresses and 

twisting caused by the piping. These stresses will 

multiply where the system is hot due to thermal ex-

pansion.

4.  If there is a high differential pressure between the 

inlet and outlet of the heat transfer system at oper-

ating temperature, this is probably due to a piping 

restriction. A continuing high differential pressure 

can cause excessive wear on the pump and pump 

stuffing box packing or mechanical seal and will 

eventually cause premature failure of the pump. 

The major causes of restrictions are:

 

a. Inlet and outlet pipes smaller than provided on 

the system.

 

b. Piping many processes in series with one anoth-

er. To reduce the pressure drop of the system, 

equipment should be re-piped in balanced paral-

lel flow.

DO provide for expansion and contraction of process 

piping and connections to the system. Piping strains 

can cause pump and motor misalignment, excessive 

wear on pump body, bearings and stuffing box packing 

or mechanical seal and will eventually cause failure of 

the pump and system.
DO provide sufficient cross sectional area in the pro-

cess piping connections equivalent to the system 

pipes. In order to prevent undue pressure drop, maxi-

mum velocity in all piping should be less than 10 feet 

per second.
DO check all vent tubes, purge valves, and bypass re-

lief valves at least once a month. All heat transfer oils 

oxidize in the presence of air and sludge can block crit-

ical piping. Blocked vent tubes may cause excessive 

system pressures and/or an explosion.
DO retighten all bolted connections and joints at oper-

ating temperature. Joints will expand and leak as they 

get hot. Check all threaded connections on controls, 

gauges, etc. for leaks.

Summary of Contents for MOS Series

Page 1: ...1 Installation Operation Manual MOS Series Hot Oil System PQ448 1 161 123417 032 September 2018 ...

Page 2: ...hase 60 cycles 50 thru 500kW In hazardous areas pipe surfaces could achieve temperatures high enough to cause auto ignition of the hazardous material pres ent Consult Article 500 of the National Elec tric Code for further information on the maxi mum allowable temperature for a specific application Unit Proportions Unit Size Dry Weight Lbs Width In Depth In Height1 In Flow Rate2 GPM Pressure2 TDH F...

Page 3: ...operation 2 The piping of the entire system should be arranged to minimize pockets where air may be trapped Manual air vents or bleeder valves should be pro vided in the system where air pockets may occur or where the flow of fluid may drop 3 Piping should be properly supported so pump can be removed without changing the position of the piping If piping moves when the pump is removed pump malfunct...

Page 4: ...essure of 2 to 3 psig 0 14 0 21 bar is maintained on pump Pump Motor The pump motor is a close coupled centrifugal pump rated for 650 F 343 C Pump and motor mounts should be checked and tightened if loosened during shipment DO provide for expansion and contraction of process piping and connections to the system Piping strains can cause pump and motor misalignment excessive wear on pump body bearin...

Page 5: ...um operating temperature is 650 F Maximum working pressure is 150 psi Horsepower requirement based on 0 85 specific gravity Maximum operating temperature is 650 F Maximum working pressure is 150 psi 100 150 kW Unit 7 5 hp 175 500 kW Unit 10 hp 50 75 kW Unit 5 hp ...

Page 6: ...ttage may be connect ed in series for operation at a higher voltage 5 The unit is completely wired The only wiring nec essary is to terminals L1 L2 and L3 in the control panel and the ground lug in the control panel Hazard of Electric Shock Disconnect all power before servicing the heat transfer sys tem 6 Jog the motor by pushing the push button marked START located on the front of the panel This ...

Page 7: ...valves 6 The temperature limiting device located inside the control panel should be checked to insure man ual reset buttons are in the closed position They should be set approximately 50 F 28 C higher than the process control during normal operation 7 Close control box door and turn circuit breaker on Start pump do not be alarmed if the pump is noisy during the initial start up operation since it ...

Page 8: ... Strainer Inlet Outlet Valves and Dedicated Fill Connections Ordering 2 or more of these options will require on site installation to avoid shipment damage The order of assembly starting at pump inlet should be gate valves strainer then fill connections A bolting kit with gaskets is provided for simple installation Please note that during operation the strainer should be checked as part of a regul...

Page 9: ...ns H System leaks at temperature and after cool down Expansion and contraction due to temperature has loosened connec tions Check all flange bolts and connections retighten and torque to manufacturer s specifications Wrong gasket materials Replace gaskets as necessary use spiral wound or Grafoil gaskets I Insufficient suction pressure 0 or vacuum pump noisy gauges vi brating discharge pressure low...

Page 10: ...ice Center 1 800 443 2640 Maximum Temperatures DO NOT attempt to operate any heat transfer system or heat transfer oil at temperatures higher than those recommended by the manufacturer Chromalox heat transfer systems are designed for a particular maximum temperature If you do not know this design temperature check with the Chromalox factory or consult the individual instruction sheet for that syst...

Reviews: