
27
Appendix
Below is the parameter settings chart organized by Menu Screen. It includes the default, minimum, maximum
and / or the range of settings, where applicable.
Parameter
Default
Min
Max
Temperature Setpoint
0˚F (-18˚C)
-80˚F (-62˚C)
1100˚F (-593˚)
Hi Temp Setpoint
200˚F (-93˚C)
-80˚F (-62˚C)
1100˚F (-593˚)
Lo Temp Setpoint
33˚F (-1˚C)
-80˚F (-62˚C)
1100˚F (-593˚)
HI Current
50 Amp
0.2 Amp
50 Amp
Lo Current
0.2 Amp
0 Amp
50 Amp
GFEP
30 mA
20 mA
150 mA
Control Mode
Manual
Manual
Auto
Output %
0
0
100
PID or ON/OFF
On/OFF
PID
On/OFF
Deadband
10
2
100
Proportional Band (%)
20
1
100
Integral
8
0
100
Derivative
2
0
500
Soft Start
Enabled
Enabled
Disabled
Wiring Considerations
• The maximum distance between ITLS panel and router can be 100m. If this distance needs to be ex-
tended it would be necessary to utilize an inline repeater.
• Cable that should be used is CAT5 RJ45 Ethernet cable.
• The HMI display has 1 Ethernet port on the back of the display (see photo below).
• Insert one end of the Ethernet cable into the HMI and the other end into customer’s network hub or
router. All HMI’s must be connected the same way.
• Typically the IP address of each HMI is assigned automatically by the DHCP Host.
• Every HMI Touch Screen Computer must have different Modbus (Slave) ID and a different IP address.
These are found on the ITLS or ITAS COMMs page.
• In order to communicate all HMI’s and the ISC Supervisory Control system must be in the same net-
work.