Adding Systems
After logging into the program with the appro-
priate security level, you may now begin to de-
sign and / or edit your intelliTRACE system.
If you wish to ADD a system, select the
Add
System
button in the bottom left of the screen.
The
System Edit form window appears.
See Figure 4.
You will be prompted to fill in the Naming, Loop
Count and the Communication Details that you
gathered for each panel that you wish to add to
your system.
System Edit & Naming Requirements:
1. Please note that each “PANEL NAME” must be a unique name throughout your entire system.
2. For the “# of Loops”, you must select the circuit count by using the drop down button. If you
manually enter the circuit count, the system will not recognize your entry.
3. The I.P. Address and the Modbus Address must match what was recorded from the respective
Panel
COMMS
Page in
Figure 4.
Select the
Save
button when you are satisfied with this System Edit form data.
The intelliTRACE screen looks the same as it did
when you first installed the program except for
the entry of your new System (or Panel).
See the new entry in both the
System Tree
Pane on the left and the Panel List on the right
in Figure 5:
Although this new System (Panel) is on your net-
work, you are not able to communicate with it
or program/change it until you
Connect to this
System (Panel).
At this point you may continue to Add more Sys-
tems (Panels) to your intelliTRACE network or
confirm communication and begin to program
each System as you add them.
To add more systems, simply repeat the
Adding
Systems procedure above.
To confirm communication and begin to program each System, go to the
Connecting Systems section.
Figure 4
Figure 5