21
Default Settings
Below is the ITC parameter settings chart organized by Menu Screen. It includes the default, minimum, maximum
and / or the range of settings, where applicable.
The chart is for either 1 or 2 circuit units.
Parameter Defaults, Min., Max. & Range & User Settings
Screen Menu & Parameter
3. Temperature Menu
Default
Min.
Max.
Also
User Settings
Temp Setpoint 1
45˚F
-80˚F
1,100˚F
Lo Temp Alarm 1
40˚F
-80˚F
1,050˚F
Off
Hi Temp Alarm 1
180˚F
-80˚F
1,150˚F
Off
Temp Setpoint 2
45˚F
-80˚F
1,100˚F
Lo Temp Alarm 2
40˚F
-80˚F
1,050˚F
Off
Hi Temp Alarm 2
180˚F
-80˚F
1,150˚F
Off
4. Current Menu
Default
Min.
Max.
Also
User Settings
Low Current Alarm 1
0.1 A
0.1 A
50.0 A
Off
Hi Current Alarm 1
40.0 A
0.1 A
50.0 A
Off
GFEP Setpoint 1
30 mA
30 mA
150 mA
GFEP Alarm/Trip 1
Alarm Only Alarm Only, Alarm & Trip; Latching & Non Latching
Low Current Alarm 2
0.1 A
0.1 A
50.0 A
Off
Hi Current Alarm 2
40.0 A
0.1 A
50.0 A
Off
GFEP Setpoint 2
30 mA
30 mA
150 mA
GFEP Alarm/Trip 2
Alarm Only Alarm Only, Alarm & Trip; Latching & Non Latching
5. Control Menu
Default
Min.
Max.
Also
User Settings
Auto Control Mode 1
PID
On / Off
PID
Auto / Manual / Off 1
Auto
0
100
Off
Deadband 1
10
2
100
Autotune 1
Off
Off
On
Proportional Band 1
20
1
100
Integral 1
500
0
9999
Rate 1
1
0
500
Soft Start 1
On
Off
On
Manual Offset 1
500
0
1000
Auto Control Mode 2
PID
On / Off
PID
Auto / Manual / Off 2
Auto
0
100
Off
Deadband 2
10
2
100
Autotune 2
Off
Off
On
Proportional Band 2
20
1
100
Integral 2
500
0
9999
Rate 2
1
0
500
Soft Start 2
On
Off
On
Manual Offset 2
500
0
1000