11
The Temperature Menu
Security Levels 1, 2 & 3
The Temperature Menu provides access to the Tem-
perature based parameters: Temperature Setpoint,
Low Temperature Alarm & High Temperature Alarm for
Circuits 1 and 2 (when available).
3. Temperature Menu
Temperature
Setpoint
Process Temperature Variable
Low
Temperature
Alarm
Lower limit of the Process Temperature
Variable at which the system goes into
alarm state. This alarm may be turned
OFF by going one increment beyond
the Lowest setting.
High
Temperature
Alarm
Upper limit of the Process Temperature
Variable at which the system goes into
alarm state. This alarm may be turned
OFF by going one increment beyond
the Highest setting.
Security Levels
You must first enter a passcode that is aligned with the
menu that you wish to access. In most cases, limited
access to certain programming areas is desired. The
most frequently used parameter settings have the low-
est level of security. Invalid passcodes will not be ac-
cepted and you will be returned to the LOGIN Screen.
Initial factory set passcodes for the Security levels be-
low are:
Security
Level
Passcode
Available
Programming Menus
1
0011
Temperature Menu Only
2
0034
Temperature & Current
Menus Only
3
0063
Temperature, Current, Control,
Comms & System Menus
You will be returned to the main screen if no buttons
are depressed within a 30 second time frame.
Passcodes may be reprogrammed within the Systems
Menu. These codes should be kept in a secure place.