38
Alarms
Alarm Types
Low & High Temperature, Low & High Current, High GFEP,
Sensor Failure, Communications, Wireless Transmitter Battery
Alarm Relay
5 Amps, Customer Supplied 2-30 VDC or 12-240 VAC
Alarm Contact State
Mode
Default
Normal Operation
Closed
Alarm Condition
Open
Power Off
Open
Communications
ModBus
RTU/RS485 (2 or 4 wire), TCP/Ethernet
Baud Rate, Hz
2400, 4800, 9600, 19200, 38400, 56000
Parity
Range: Even, Odd, None
ModBus ID
Range: 1 – 255
BacNET
Available, Contact Sales
Operating & Environmental
Temperature
-40˚F to 104˚F (-40˚C to 40˚C) *Enclosure heater required for below 0°C (32°F)*
Humidity
Relative Humidity 0% to 90%
Power Supply
100-600 Vac 50/60Hz
Protection
IEC IP66 (Front Panel)
Enclosure Rating
NEMA 4 or Optional NEMA 4X 304SS
Approvals
UL/cUL Ordinary and Class I, Division 2, Groups A,B,C,D Hazardous loca-
tions (UL file Number: E165116)
Temperature Rating
T4 (Derate to T3 & Groups B,C,D when using enclosure heater)
Default Settings
Below is the parameter settings chart organized by Menu Screen. It includes the default, minimum, maximum and/
or the range of settings, where applicable.
Parameter
Default
Min
Max
Temperature Setpoint
0˚F (-18˚C)
-80˚F (62˚C)
1100˚F (593˚C)
Hi Temp Setpoint
200˚F (93˚C)
-80˚F (62˚C)
1100˚F (593˚C)
Lo Temp Setpoint
32˚F (0˚C)
-80˚F (62˚C)
1100˚F (593˚C)
HI Current
50 Amp
0.2 Amp
50 Amp
Lo Current
0.2 Amp
0 Amp
50 Amp
GFEP
30 mA
20 mA
150 mA
Control Mode
Manual
Manual
Auto
Output %
0
0
100
Integral
8
0
100
Derivative
2
0
500
PID or ON/OFF
On/OFF
PID
On/OFF
Soft Start
Enabled
Enabled
Disabled