Using Hysteresis – The outputs will untrip when the input value exits the hysteresis
(deadband) limit.
Note: The order of precedence for the methods of untrip is Manual Reset Only,
Pressing Enter, and then Using Hysteresis. This means that if at any time an output is
tripped and configured by an zone to untrip using Manual Reset Only, the only way to
untrip that zone is using the Manual Reset.
Note: When any zone causes a trip for an output, all zones that have caused a trip on
that output will be refreshed. This means that if an output has been tripped and then
cleared by pressing Enter and another zone causes that output to retrip, the output
will act as though both trips have reoccurred at the same time to cause the output to
trip. So, if the second trip were to reset by dropping below the programmed
hysteresis value, the output will still be tripped, due to the first zone, which caused the
trip. To reset the output again, Enter would need to be pressed.
Set Hysteresis:
- Hysteresis is the amount that the reading must move past the trip
value before the outputs will reset. For example, the system is configured to trip at
100ºF, has a 10ºF hysteresis and will trip Output 1 on an over temperature reading.
The reading increases to 100ºF, so Output 1 trips. The reading will need to go below
90ºF before Output 1 will reset.