Wiring the Chroma-FP1-OD
Heater load connection
Provide terminals L, N with up to 120 VAC, 30 AMP.
Make sure the wire Gauge (AWG) is suitable for the circuit Amperage draw, as specified in the NEC/
CEC table 1.
Pg. 5
Heater
Load
connection
120 VAC, 30A
Branch circuit protection
and disconnect provided
by installer. Max. 30A
L
L
N
N
NO NC HE
Heat
Indication
(24VAC)
Chroma-FP1-OD
Caution: Incorrect voltage may cause fire or seriously damage the unit.
Heater
Load
connection
120 VAC, 30A
CS-HL
Upper limit
sensor
(By Chromalox)
L
L
N
N
NO NC HE
C
C
1
2
Aquastat
(option)
Heat
Indication
(24VAC)
*GFEP Indication - Dry Contact / Alarm
Main
Supply
120 VAC
Chroma-FP1-OD-AB
Branch circuit protection
and disconnect provided
by installer. Max. 30A
Main
Supply
120 VAC
GFEP
Indication
Dry Contact
(NO/NC)
*See table
GFEP
Indication
Dry Contact
(NO/NC)
*See table
GFEP Tripped
GFEP NOT Tripped
NO - COM
NC - COM
SHORT
OPEN
OPEN
SHORT
CS-HL
Upper limit
sensor
(By Chromalox)
C
C
1
2
Aquastat
(option)
A
B
BMS
(BACnet/Modbus)
or Wi-Fi module
Chroma-FP-OD Series
Owner’s manual & Technician Settings
1-800-443-2640
www.chromalox.com