Technician settings (Cont’)
Pg. 13
P09 - Test conditions mode / Technician commissioning mode
Turn ON test conditions to check the functionality of the system regardless of
temperature sensors parameters (i.e. during the summer).
In test conditions, the Ambient temperature is always -7°C/19°F.
Press the [SELECT] and [+] buttons simultaneously.
“P09” will appear on display. The hours will blink.
Use the [+] button to enter test/commissioning mode – the word “Test” will
appear on display.
Use the [-] button to manually exit test/commissioning mode – the word
“Test” will disappear from display.
Note: If the technician did not manually exit test/commissioning mode, the unit
will automatically return to normal mode after 5 hours.
Test
conditions
mode
P15 – Temperature sensor calibration offset
Press the [SELECT] and [+] buttons simultaneously.
“P10” will appear on display.
Use the [+] button to adjust the offset for calibration of measured temperature.
Range: -9…+9°F / -6…+6°C
Default: 0°F / 0°C
Note: If the technician did not manually exit test/commissioning mode, the unit will
automatically return to normal mode after 5 hours.
Offset
P11 – Master/Slave
Press the [SELECT] and [+] buttons simultaneously.
“P11” will appear on display.
Use the [+] and [-] buttons to select between:
- “
Π
A” - Master (When using one Chroma-FP-OD or when controlling other
Chroma-FP-OD devices connected to A,B as slaves) - default
- “SL” - Slave (controlled by another Chroma-FP-OD connected to A,B)
Slave
Master
Chroma-FP-OD Series
Owner’s manual & Technician Settings