Chromalox CES-100 Installation, Operation And Renewal Parts Identification Download Page 14

OPTIONAL EQUIPMENT FOR STEAM BOILERS

AUXILIARY LOW WATER CUTOFF
Operation

Operation of this control is accomplished by sensing a minute AC

current flowing between submerged contact probe in the boiler shell.

When this minute AC current is conducted through an external cir-

cuit resistance up to 40,000 ohms or less, a signal of sufficient magni-
tude is present to trigger the SCR and, in turn energize the control
relay.

As the water level in the boiler drops below the level of the probe,

the AC current is broken and the control relay is de-energized. The
control will not energize until sufficient water is present in the boiler.
Optional manual reset may require reset prior to heaters being ener-
gized after level 13 brought to normal.

WARNING:

Control will not work with de-ionized or de-

mineralized water.

PROPORTIONING PRESSURE CONTROL FOR
SEQUENCER AND SCR CONTROLS
Typical Operation

Pressure variations cause the bellows to expand or contract.

Linkage between the bellows and the potentiometer wiper causes the
wiper to move across the windings on the potentiometer. This varies
the resistance between R and B, and between R and W, causing an
unbalance in the circuit connected to the controller.

A proportioning pressure control is used to regulate a motor driven

or solid state sequencer. The controller potentiometer, the feedback
potentiometer in the motor and a balancing relay in the motor form an
electric bridge circuit. As long as the pressure of the controlled medi-
um remains at the set point of the controller, the circuit is balanced;
i.e., equal currents flow through both sides of the balancing relay and
the relay contacts are open. When the circuit is balanced, the motor
does not run.

If the pressure of the controlled medium rises, the wiper in the con-

troller moves toward W. This unbalances the circuit so a larger current

flows through one side of the balancing relay. The “close” contacts in
the relay make, causing the motor to drive toward its closed position. As
the motor runs, the wiper on the feedback potentiometer moves in a
direction to balance the circuit. When the circuit is again in balance, the
balancing relay contacts open and the motor stops.

Similarly if the pressure of the controlled medium falls, the wiper on

the controller potentiometer moves toward B, and the “open” contacts
in the balancing relay make. The motor drives towards its open position
until circuit balance is achieved.

The slightest change in the pressure of the controlled medium will

cause a change in the number of elements energized to compensate for
it, thus keeping the pressure constant. This process is called modulation.

PROPORTIONAL PRESSURE CONTROL ONLY SUPPLIED
WITH SEQUENCER

Main Setting — 

Turn the adjustment screw until the indicator is

opposite the low point of the desired throttling range. That is, if the pres-
sure is to be held at a minimum of 50 psi, set the indicator at 50 psi. The
pressure will them be maintained between 50 psi and a higher pressure
equal to the 50 psi plus the throttling range.

THROTTLING RANGE SETTING (L91B)

After setting the indicator for the minimum pressure, turn the throt-

tling range adjustment screw until the throttling range indicator points to
the desired throttling range on the scale. This scale is graduated from
“min” to “F”. The value of each division varies with the scale range of
the instrument.

PRESSURE

VALUE EACH

SCALE RATING

DIVISION ON SCALE

0-15 psi

2.2 psi

5-150 psi

3.6 psi

Pressure scale rating will vary depending on pressure control supplied.

CHECKOUT

After the controller has been installed, wired, and set, it should be

tested with the system in operation. First allow the system to stabilize.
Then observe the operation of the controller while raising and lowering
its set point. Pressure should increase when the set point is raised and
decrease when the set point is lowered. Use accurate pressure testing
equipment when checking out the controller. Do not rely on inexpensive
gauges. The controllers are carefully calibrated at the factory.

If the motor or actuator runs the proper direction when the set point

is adjusted, it can be assumed that the controller is operating properly. If
it runs in the wrong direction, reverse the B and W wires. Observe the
action of the motor to see if it stabilizes. If the motor is moving con-
stantly, widen the proportioning range a little at a time, until the system
is stable.

14

Adjusting Screw

Differential Adjusting Screw

R

W

B

(L91B)
Proportioning Pressure Control used with Sequencer Control

3

3

2

2

2

2

6

6

2

2

1

1

LWCO Probe

Aux. Low

Water Cutoff

O

O

O

R

H

C

1PS

C1 NO

L1 L2

1PS

BL

W

Y

2PS

BL

Auto

Blow

Down

System

BR

C1

W

W

Heater

Contactor

Feed Water

(Solenoid Pump)

R

1LT

W

Boiler On

2

GND

3

GND

1

GND

B

FU3

B 1PB On

Off

X1

X3 X2 X4

1 HTR

C1

Fuses Supplied

on Boilers Rated

Over 40 Amps.

FU

FU

FU

FU2

FU1

H1

H2

H3

H4

480V/120V

1.5 KVA

480V

3

60 HZ

L1

L3

L2

Typical Wiring for

Auxiliary Low Water Cutoff

Electronic Resistance Sensing

Amplifier for Auxiliary

Low Water Cutoff

Summary of Contents for CES-100

Page 1: ...3 50 6 17 CES 135 13 9 136 30 5 410 8 50 4 50 8 17 1 30 CES 160 16 1 157 5 30 5 475 7 60 3 60 7 22 5 CES 180 18 4 180 30 5 543 8 60 4 60 8 22 5 Chromalox DIVISION 4 SECTION CES SALES REFERENCE DATE SE...

Page 2: ...nection Conduit Box Element I Steam Outlet Sight Glass Element Access Door 5 8 7 16 Bolt Hole typical Drain Blowdown Valve K A B C Check Valve D H F E G Operating Pressure Control Safety Valve Outlet...

Page 3: ...ust be main tained 3 Complete all piping to boiler Connect water line to tagged fitting on the motor and pump assembly if used or to tagged fitting on water control feeder 4 When any type of feed othe...

Page 4: ...ed 6 WARNING Substitution of components or modifica tion of wiring system voids the warranty and may lead to dangerous operating conditions 7 SPECIAL INSTRUCTIONS FOR CUSTOMERS SUPPLY ING THEIR OWN CO...

Page 5: ...R C2 FU4 FU5 FU6 2L1 2L3 2L2 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 3 2PS BR Heater Contactor Feed Water Boiler On 3 GND B FU6 B 1PB Off 1 GND 1 HTR C...

Page 6: ...3 C2 FU7 FU8 FU9 C3 3L1 1L3 3L2 3 HTR C3 Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 5 2PS BR Heater Contactors Feed Water Boiler On 3 GND...

Page 7: ...C3 C4 FU 10 11 12 4 Htr FU10 FU11 FU12 C4 4L1 4L3 4L2 4 HTR C4 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 7 2PS BR Heater Contactor Feed Water Boiler On...

Page 8: ...ND Cabinet Exterior Left Side Cabinet Exterior Right Side Panel Layout Feed Water Electrical Connection Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 9 FU 1...

Page 9: ...H1 H4 H2 H3 FU24 FU23 FU22 FU21 FU20 FU13 C8 C7 7 HTR 6 HTR 7L1 8L3 8L2 8L1 5L3 7L2 C5 C7 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 11 FU 1 2 3 FU 4 5 6...

Page 10: ...7L2 FU FU FU C7 C6 Heater Contactor Heater Contactor Heater Contactor Heater Contactor Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 13 FU...

Page 11: ...in valve or release man ual blowdown switch If low water cutout is automatic reset pump or solenoid will return water level to normal If low water cutout is manual reset then manual reset button on Mc...

Page 12: ...ustomer Supplied 2 Turn on boiler and allow pressure to build up to operating pressure 3 Only open globe valve at quarter turns at first introducing smaller amounts of steam into process Avoid opening...

Page 13: ...E CLOSED and the BOILER ON should light up again Now turn the wheel on the large timer until the OFF tab passes the TIME NOW arrow The BOILER ON light should go out and the valve should begin to open...

Page 14: ...circuit balance is achieved The slightest change in the pressure of the controlled medium will cause a change in the number of elements energized to compensate for it thus keeping the pressure constan...

Page 15: ...stage loads of the type used in Chromalox steam boilers It features progressive sequencing first on first off which equalizes the operating time of each load This control gives visual indication of e...

Page 16: ...ed 3 Connect piping from discharge to water inlet check valve on boil er with minimum of 90 bends or other restrictions 4 All electrical wiring should be done by licensed electricians in accordance wi...

Page 17: ...sure to drop to zero before ser vicing WARNING Provision should be made to prevent water damage from any eventual leaking of boiler or com ponents Install near a floor drain 2 On automatic feed units...

Page 18: ...end life 2 If generator is undersized for its application heaters will be over worked and reach end of life sooner 3 Element has been overheated due to excessive scale build up The scale acts as an i...

Page 19: ...50Hz 193 300175 002 Motor only used in ES 38020 115V 60Hz 193 300175 004 Strainer used in ES 38020 351 118664 001 V Band Mount used in ES 38002 ES 38020 355 300174 001 Solenoid Valve used in ES 38002...

Page 20: ...0 amp 600V 128 121133 066 60 amp 600V 128 121133 067 Fuse Block 35 60 amp 60 amp 600V 129 047445 002 Power Terminal Blocks 3 pole 115 amp 1 line circuit 1 load circuits 303 071809 032 3 pole 175 amp 1...

Reviews: