Chromalox CES-100 Installation, Operation And Renewal Parts Identification Download Page 13

OPERATION

AUTOMATIC BLOWDOWN INSTRUCTIONS
(IF FURNISHED)

The Automatic Blowdown is a device which automatically starts

up your boiler in the morning; shuts it down at night and blows down
(partially drains) the main boiler drain and the low water cut-off col-
umn for a predetermined time interval each working day.

The heart of the unit is an electrically operated straight through

type ball valve. It is specially designed to handle dirty, corrosive flu-
ids and particles without requiring cleaning or the use of a strainer.

Both the valve and the boiler are controlled by an electric control

unit which indicates with pilot lights when the drain valve is in the
opened or closed position and when the boiler is ON or OFF. In addi-
tion to the automatic control function, the unit has a push button which
momentarily de-energizes the boiler and opens the drain valve regard-
less of the time of day.

The unit may also be used to blow down boilers which run con-

tinuously, day and night.

INITIAL TESTING — 

Set the switch marked “Programmed

duty/24 Hour duty” located on the panel box to the “ON” position.

On the large timer set the “ON” tab at about 8 AM and the “OFF”

tab at about 8 PM. Set the blowdown cycle dial at “O”.

Turn the large timer by hand until the “ON” tab passes the “TIME

NOW” indicator so the “TIME NOW” arrow indicates 10 AM.

Energize the main feed to the “LINE TERMINALS” of the unit.

The “BOILER ON” pilot light as well as the “VALVE CLOSED”
light should glow.

Hold down the “DRAIN” button for about six seconds. The

“BOILER ON” light should go out immediately as well as the
“VALVE CLOSED” light. It takes about 4 seconds for the drain valve
to open fully at which time the “DRAIN VALVE OPEN” light should
light. As soon as the “DRAIN” button is released the valve begins to
close. When it reaches the closed position, the “VALVE CLOSED”
and the “BOILER ON” should light up again.

Now turn the wheel on the large timer until the “OFF” tab passes

the “TIME NOW” arrow. The “BOILER ON” light should go out and
the valve should begin to open. Once the “VALVE OPEN” light goes
on, the valve should remain open for a few seconds and then auto-
matically close. The “VALVE CLOSED” light should light and the
“BOILER ON” light should remain off.

OPERATION—

Set the “BOILER PROGRAMMED DUTY”

switch to “BOILER ON” if the boiler is to be shut down each night.
Set it to “24-HOUR DUTY” if the boiler is to remain  on continuous-
ly 24-hours per day (except during blowdown).

Set the tabs on the large timer for the ON and OFF times desired

for the boiler, screw in the small black day-skip tabs if is to remain off
during the weekend, etc.

If the boiler is on 24-hour duty, set the OFF tab for the time that is

desired for blowdown. the ON tab can be ignored, but must remain on
timer.

The small time delay relay controls the time that the drain valve

remains open. The time is controlled by adjusting knob marked
Blowdown cycle. Counterclockwise decreases, clockwise increases
blowdown time. Time must be adjusted by trial.

13

Boiler On

Valve Open

Valve Closed

Programmed Duty

24 Hour Duty

Manual Drain

Valve Actuator

Timer

Automatic Blowdown Control Cabinet

Display View of Automatic Blowdown Control Cabinet

Terminal Block

Support

7 Day Clock

Control

Relay

Time Delay Relay

311

7

2

10

2

6

28

Terminal Block

Component Layout

Support

Replace with

Amp Fuse Only

Manual Drain

24 Hour Duty

Prorammed Duty

Valve Open

Valve Closed

Boiler On

Blowdown Cycle

30's

0's

80's

Cycle 

Adjustment

On/Off Switch

Indicator Light

Indicator Light

Switch

PB Switch

Fuse

Valve Closed

Boiler Control

(3)

Boiler On

Ball Valve

Control

(5)

7-Day Timer

(2.3)

Exterior Side

2

w

Clock

3A

1

8

1LT

2LT

3LT

0

Valve Open

Blowdown Valve

Motorized

6

Y

B

2A

1A

2B

1B

BL

2

3

4

2

3

4

1

2

1

P

2PB

1PB

1CL

1CL

1TR

PR

1CR

G

3

B

1FU

15A

7

R

B

10

1CR

1TR

1

R

R

8

2

W

O

R

/

M

OBL

/

R

11

Wiring Diagram for Automatic Blowdown

Summary of Contents for CES-100

Page 1: ...3 50 6 17 CES 135 13 9 136 30 5 410 8 50 4 50 8 17 1 30 CES 160 16 1 157 5 30 5 475 7 60 3 60 7 22 5 CES 180 18 4 180 30 5 543 8 60 4 60 8 22 5 Chromalox DIVISION 4 SECTION CES SALES REFERENCE DATE SE...

Page 2: ...nection Conduit Box Element I Steam Outlet Sight Glass Element Access Door 5 8 7 16 Bolt Hole typical Drain Blowdown Valve K A B C Check Valve D H F E G Operating Pressure Control Safety Valve Outlet...

Page 3: ...ust be main tained 3 Complete all piping to boiler Connect water line to tagged fitting on the motor and pump assembly if used or to tagged fitting on water control feeder 4 When any type of feed othe...

Page 4: ...ed 6 WARNING Substitution of components or modifica tion of wiring system voids the warranty and may lead to dangerous operating conditions 7 SPECIAL INSTRUCTIONS FOR CUSTOMERS SUPPLY ING THEIR OWN CO...

Page 5: ...R C2 FU4 FU5 FU6 2L1 2L3 2L2 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 3 2PS BR Heater Contactor Feed Water Boiler On 3 GND B FU6 B 1PB Off 1 GND 1 HTR C...

Page 6: ...3 C2 FU7 FU8 FU9 C3 3L1 1L3 3L2 3 HTR C3 Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 5 2PS BR Heater Contactors Feed Water Boiler On 3 GND...

Page 7: ...C3 C4 FU 10 11 12 4 Htr FU10 FU11 FU12 C4 4L1 4L3 4L2 4 HTR C4 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 7 2PS BR Heater Contactor Feed Water Boiler On...

Page 8: ...ND Cabinet Exterior Left Side Cabinet Exterior Right Side Panel Layout Feed Water Electrical Connection Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 9 FU 1...

Page 9: ...H1 H4 H2 H3 FU24 FU23 FU22 FU21 FU20 FU13 C8 C7 7 HTR 6 HTR 7L1 8L3 8L2 8L1 5L3 7L2 C5 C7 Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 11 FU 1 2 3 FU 4 5 6...

Page 10: ...7L2 FU FU FU C7 C6 Heater Contactor Heater Contactor Heater Contactor Heater Contactor Heater Contactor Wire Color Code B Black BR Brown R Red O Orange Y Yellow G Green BL Blue W White Diagram 13 FU...

Page 11: ...in valve or release man ual blowdown switch If low water cutout is automatic reset pump or solenoid will return water level to normal If low water cutout is manual reset then manual reset button on Mc...

Page 12: ...ustomer Supplied 2 Turn on boiler and allow pressure to build up to operating pressure 3 Only open globe valve at quarter turns at first introducing smaller amounts of steam into process Avoid opening...

Page 13: ...E CLOSED and the BOILER ON should light up again Now turn the wheel on the large timer until the OFF tab passes the TIME NOW arrow The BOILER ON light should go out and the valve should begin to open...

Page 14: ...circuit balance is achieved The slightest change in the pressure of the controlled medium will cause a change in the number of elements energized to compensate for it thus keeping the pressure constan...

Page 15: ...stage loads of the type used in Chromalox steam boilers It features progressive sequencing first on first off which equalizes the operating time of each load This control gives visual indication of e...

Page 16: ...ed 3 Connect piping from discharge to water inlet check valve on boil er with minimum of 90 bends or other restrictions 4 All electrical wiring should be done by licensed electricians in accordance wi...

Page 17: ...sure to drop to zero before ser vicing WARNING Provision should be made to prevent water damage from any eventual leaking of boiler or com ponents Install near a floor drain 2 On automatic feed units...

Page 18: ...end life 2 If generator is undersized for its application heaters will be over worked and reach end of life sooner 3 Element has been overheated due to excessive scale build up The scale acts as an i...

Page 19: ...50Hz 193 300175 002 Motor only used in ES 38020 115V 60Hz 193 300175 004 Strainer used in ES 38020 351 118664 001 V Band Mount used in ES 38002 ES 38020 355 300174 001 Solenoid Valve used in ES 38002...

Page 20: ...0 amp 600V 128 121133 066 60 amp 600V 128 121133 067 Fuse Block 35 60 amp 60 amp 600V 129 047445 002 Power Terminal Blocks 3 pole 115 amp 1 line circuit 1 load circuits 303 071809 032 3 pole 175 amp 1...

Reviews: