6. Replacing Output Modules

The Chromalox 2110 Temperature Controller was 

shipped with the output modules installed as ordered. 

The 10A Solid State Relay and 20A Mechanical Re-

lay output cards control small cartridge heater or strip 

heater loads directly, eliminating the need for a remote 

contactor or solid state relay. If a larger load is required, 

the 2110 can be configured with a 1A Pilot Duty Relay 

or Solid State Relay Drive.

The 2110 may be optionally configured with a 5A/120V 

Alarm Relay. Alternate modules, configured with or 

without alarm, can be installed as needs change.
Control and alarm outputs can be changed in the field.

Module Option Descriptions

Output Module options are as follows:

Menu Code

Function

Adjustable 

Range

Factory 

Default

Security 

Level

R1 Relay 

Form A contact, SPST, N.O. 1.0 Amp at 120/240 

VAC resistive load 

30 sec. 

0149-27133  0149-27147 

R3 Relay 

Form A contact, SPST, N.O. 20 Amp at 240 VAC, 

28 VDC resistive load 

30 sec. 

0149-27132  0149-27146 

V0 SSR Drive  24 VDC nominal at 40 mA 

1 sec. 

0149-27135  0149-27149 

S1 TRIAC 

1 amp continuous, 10 Amp in-rush 120/240 VAC 

1 sec. 

0149-27134  0149-27148 

S1 Solid State 

Power Controller  120/240 VAC, 5 Amp @ 40°C ambient 

1 sec. 

0149-27136  0149-27150 

S2 Solid State 

Power Controller 

120/240 VAC, 10 Amp @ 40°C ambient with 

built-in cooling fan mounted on rear of housing 

1 sec. 

0149-00022 

(Fan Kit) 

0149-00022 

Module Installation

Remove power from the controller before 

changing the output module. Failure to do so 

could cause damage to controller and/or per-

sonal injury or death from electrical shock.

When handling output modules, be careful to guard the 

module against static discharge. Follow the steps be-

low to remove an existing output module and replace it 

with a new module.
Removal
1.  Remove power from the controller.
2.  Remove all terminal connections.
3.  Remove the back cover by lifting four housing clips 

on the controller. This releases the back cover. Then 

pull cover straight off the controller.

4.  Gently pry around the sides to loosen and remove 

the module. Pull module straight out to avoid bend-

ing pin connections.

Do not remove module by the handling compo-

nents on the module board. This could damage 

the module.

  When removing an S2 output module (SSR with 

fan), a cable connects the fan to the far right center 

of the S2 board. Gently disconnect the cable from 

the connector on the output board. 

Do not remove 

the fan from the back cover. This is a single as-

sembly.

  For the S2 output module, reconnect the fan cable 

to the connector on the far right center of the mod-

ule. Tuck the cable around the heatsink.

Replacement
1.  Line up pins on the controller with pin connections 

on either side of the module and push the new mod-

ule into place.

2. Reinstall the back cover.

Summary of Contents for 2110

Page 1: ...i PK498 2 0037 75409 March 2020 Instruction Manual 2110 Temperature Controller ...

Page 2: ...unting Collars 4 3 3 Mounting Dimensions 4 3 4 Mounting the 2110 4 3 5 Wiring Terminal Identification 4 3 6 Thermocouple Connections with Shield 6 3 7 Three Wire RTD Connections with Shield 6 3 8 Two Wire RTD Connections 6 3 9 Control Output Wiring R1 and S0 7 3 10 Control Output Wiring R3 7 3 11 Control Output Wiring V0 7 3 12 Control Output Wiring S1 and S2 7 3 13 90 260 VAC Instrument Power Con...

Page 3: ...he unit 2 To adjust the set point on the Chromalox 2110 Tem perature Controller press and hold the Set Point button see Figure 1 2 The Set Point light is illumi nated 3 While still pressing the Set Point button press either the d or f button to adjust the set point to the de sired value see Figure 1 3 Holding the dor fbut ton increases the speed of the set point changes Figure 1 2 Establishing the...

Page 4: ...Ds Actual process temperature displayed LEDs Indicates F or C selected for temperature display In Operation Mode pushbuttons adjust Set Point In Setup Mode pushbuttons increase decrease MENU values Set Point Button In Operation Mode adjusts Set Point In Configuration Mode with the or button serves as Menu button Load Alarm F C Temp Point Set Point Chromalox 2110 Inspection Unpacking Your Chromalox...

Page 5: ...ts Code Control Output R1 Relay 1 Amp Form A 120 240Vac R3 Relay 20 Amps Form A 120 240Vac V0 Solid State Relay Drive 24Vdc 40ma S0 Solid State Relay 1 Amp up to 240 Vac S1 Solid State Relay 5 Amps up to 240Vac S2 Solid State Relay 10 Amps up to 240Vac Code Alarm Output Kit Option 0 No Alarm 1 Alarm Form C Relay 5 Amps at 120Vac 2 5 Amps at 240Vac Code 0 Add to Complete Part Number Code Power Supp...

Page 6: ... selects input type thermocouple or RTD resistance temperature detector Note If RTD is se lected switch A is ignored Switch C selects temperature units F or C Switch D selects either PI Proportional Integral or ON OFF control Figure 3 1 Default Dip Switch Settings J RTD C ONOF K TC F PI J RTD C ONOF K TC F PI Mounting Two mounting collars securely hold the 2110 controller in the mounting hole Remo...

Page 7: ...al noise can affect the function of any control system When driving a contactor coil or other induc tive load an appropriate rated AC snubber circuit is recommended Chromalox Part No 0149 01305 Connect before power is applied Make all electrical wiring connections to the back of the controller before power is applied to the unit Comply with regulations All wiring practices must comply with local r...

Page 8: ...pe Material Polarity Polarity J iron constantan white red K chromel alumel yellow red Make thermocouple wiring connections to terminals as shown in Figure 3 6 Figure 3 6 Thermocouple Connections with Shield TC NC NO COM TC Shield Ground Three Wire RTD Inputs IMPORTANT When making the three wire RTD input connection make the resistance of all three extension leadwires equal by using the same gauge ...

Page 9: ... Solid State Relay Drive 24Vdc 40mA Output Wiring NC NO COM Fuse Load Snubber 120 240 VAC Neutral Fuse Load 120 240 VAC Neutral NC NO COM NC NO COM NO COM NC NO COM Fuse Load 120 240VAC AC Neutral SSR 4115 V0 Solid State Relay Drive 24Vdc 40mA Output Wiring Figure 3 9 Control Output Wiring R1 and S0 Figure 3 10 Control Output Wiring R3 Figure 3 11 Control Output Wiring V0 R3 20 Amp Relay Output Wi...

Page 10: ... justment See Figure 4 4 3 Press and hold the Set Point button and press the dor fbuttons to scroll the configuration menus The display will show the name of the menu and then begin to toggle between the name and the current value See Figures 4 5 and 4 6 4 Press the or buttons to adjust the value only the value is displayed during adjustment See Figure 4 7 The new value is set when the or button i...

Page 11: ...y when the dip switch is set to PI 1 to Sensor Span Maximum F or C 25 B ArSt Automatic Reset Control feature that automati cally corrects for small temperature offsets that occur in proportional control The higher the setting the faster the correction occurs A high setting could cause overshoot during start up A low setting will not allow process temperature to reach to set point quickly enough A ...

Page 12: ...mit to which set point may be set without security code access Sensor Range F or C Span Low B SPUL Set Point Upper Limit Upper limit to which set point may be set without security code access This prevents an operator from setting the set point temperature to a level which would dam age equipment or process Sensor Range F or C Span High B outl Output Limit Limits the percentage of output that can ...

Page 13: ...w often to switch the output to the heater For example if the cycle time is 1 second and the 2110 needs a 75 out put the output will be on for 3 4 of a second and off 1 4 of a second Units with relay control outputs R1 or R3 are shipped with a 30 second cycle time Units with solid state relays or solid state relay drives S0 S1 S2 or V0 are shipped with a 1 second cycle time Alarm Operation optiona...

Page 14: ...0 C ambient with built in cooling fan mounted on rear of housing 1 sec 0149 00022 Fan Kit 0149 00022 Module Installation Remove power from the controller before changing the output module Failure to do so could cause damage to controller and or per sonal injury or death from electrical shock When handling output modules be careful to guard the module against static discharge Follow the steps be lo...

Page 15: ...table on page 17 After replacing a control output the 2110 verifies at power up if a slow or fast cycle time output has been installed If an output with a different default cycle time is installed the 2110 will change the cycle time to the new device s default If the user has changed the cycle time in configuration the 2110 retains this value unless an output with a different default cycle time ha...

Page 16: ...al calibration for a single sensor Calibration Notes When calibrating the 2110 1 You must have a sensor simulator to calibrate the 2110 controller Substitute a precision sensor simu lator Thermocouple simulator or resistance simula tor box for sensor inputs 2 Disconnect load power to prevent damage to the process or load 3 Calibrate RTD inputs using copper Cu wire Cali brate thermocouple inputs us...

Page 17: ...o 240VAC at 40 C Solid State Relay S2 10A up to 240VAC at 40 C Alarm Form C Relay 5 Amps at 120VAC 2 5A at 240VAC Sensor Input Switch selectable J K Thermocouple RTD Input Update Rate Four samples per second Input Specifications Range F Range C Accuracy at 77 F ambient J TC 100 to 1400 F 73 to 760 C 0 2 Span 1 least significant digit K TC 100 to 2400 F 73 to 1316 C 0 2 Span 1 least significant dig...

Page 18: ...sensor input to earth ground Series Mode Noise Less than 2 F with 100mV peak to peak series mode noise RFI Typically less than 0 5 of sensor span at distance of 1 meter 3 1 feet from a transmitter of 4W at 464MHz Sensor Leadwire Effect J Thermocouple 1 F for 1000 ft of 18 AWG thermocouple extension wire K Thermocouple 2 F for 1000 ft of 18 AWG thermocouple extension wire RTD 0 1 of sensor span per...

Page 19: ... fuse is not open 3 Verify output limit is set to 100 4 Verify set point is greater than process temperature 5 Verify output wiring Erratic operation 1 Intermittent sensor connections 2 Controller failure internal electronics 3 External electrical noise 1 Check sensor wiring or substitute sen sor simulator 2 Power down and repower up 3 Contact Chromalox Process not in control 1 Incorrect settings ...

Page 20: ... the Chromalox limited warranty applicable to this product at http www chromalox com customer service policies termsofsale aspx 2020 Chromalox Inc Chromalox Inc 1347 Heil Quaker Boulevard Lavergne TN 37086 615 793 3900 www chromalox com ...

Reviews: